BTRM Battery Test Remote Monitoring System – User Guide V3.2 |
ã
2021 Ventev | LIT SKU: 09834
17
9. Port Options Page
This allows the user to enable the IO channels and the system operation voltage.
Note that the BTRM400 has additional system voltages for 36V and 48V operation.
9.1
IO Channel 1
9.1.1
Analog Input 0-32V
This allows the user to enable an analog input level for triggering alarms from external
sources (door switches, solid state relays, etc.).
9.1.2
Digital Input Alarm if < 1V
This allows the user to enable a digital input logic levels that is less than 1 volt to trigger
an alarm from external sources (door switches, solid state relays, etc.).
9.1.3
Digital Input Alarm if > 2V
This allows the user to enable a digital input logic levels that is greater than 2 volt to
trigger an alarm from external sources (door switches, solid state relays, etc.).
9.1.4
Low Capacity Alarm
This allows the user to enable the channel relay to indicate a battery relate fault
•
Digital Out Normally Open: The relay closes when a fault is indicated.
•
Digital Out Normally Low: The relay opens when a fault is indicated.