BTRM Battery Test Remote Monitoring System – User Guide V3.2 |
ã
2021 Ventev | LIT SKU: 09834
42
13.6
Function 06 Holding Register | Write Single
14. Additional Network Setup
14.1
IP Reset
To reset the device to its default IP address settings, hold Button PB1 for 20 seconds. All the
LEDs will flash, and the unit will restart with the default IP settings listed on the device label.
Typically, these settings are:
Unit IP
192.168.1.214
Subnet Mask
255.255.255.0
Gateway
192.168.1.1
Additionally, the IP reset function resets the Authorizations settings to Default
14.2
Router Ports
If you need to access the device from outside of a local intranet (hosts computer is on the
WAN side of the device router), the appropriate ports will need to be set on the router to
which the host computer is attached and also the router to which the device is attached.
One solution:
Routers allow a single device to be set so that it can be reached by using the router’s IP
address. The same can be done for the host computer, sometimes called “placing the device
in the demilitarized zone” (DMZ). Not as secure, but much simpler as ports do not need to be
forwarded. In this case the device IP
ó
the Router WAN IP.
Opening Ports Method:
When accessing the device from behind a router the device LAN IP address is effectively
hidden. In this case the port number is used to determine the final destination. Only the WAN
IP address of the router is reachable. The host computer then uses the router WAN IP as the
destination IP address.
The Router then uses the messages destination port, and the routers port forwarding table to
direct to the appropriate device on the internal intranet.
For example:
Host Computer has internal LAN IP of 192.168.1.214
Its Router has WAN IP of 100.78.60.21
Device issues a SNMP notification to 100.78.60.21:162 (where 162 is the port number)
Point Description
State
Value
0
Battery Minimum Runtime
Minutes
1
Battery Test Schedule Time
Hours
2
Battery Test Next Test Time
Hours
3
Aux IO Channel 1 Config
1,2,3
4
Aux IO Channel 2 Config
1,2,3,4,5
5
System Selection 12V /24V
1,2 (12v/24v)
12v/24v