12.3.6
Analog Input Status Points
Point
Description
Units
0
Battery Voltage
Millivolts
0 to3200 mv
1
Charger Voltage
Millivolts
0 to3200 mv
2
Battery Current
±Milliamps
± 32000 ma
3
Temperature
±°C
4
Battery Minimum Runtime
Minutes
0 to 3200 minutes
5
Battery Runtime Estimate
Hours
6
Battery Test Temperature
±°C
7
Battery Test Schedule Time
Hours
0 to 500 hrs
8
Battery Test Next Time
Hours
0 to 500 hrs
9
Aux IO Channel 1 Voltage
Millivolts
0 to3200 mv
10
Aux IO Channel 2 Voltage
Millivolts
0 to3200 mv
11
Firmware Version
format xx.xx -> 130 = v1.30
12.3.7
Analog Output Status Points
Point
Description
State
0
Battery Minimum Runtime
Minutes
0 to 3200 minutes
1
Battery Test Schedule Time
Hours
0 to 500 hrs
2
Battery Test Next Test Time
Hours
0 to 500 hrs
3
Aux IO Channel 1 Config
1,2,3
(see below)
4
Aux IO Channel 2 Config
1,2,3,4,5
(see below)
5
System Selection 12V /24V
1,2
1= 12v, 2 =24v
IO1
Function Control
Values 0,1,2,3,4
Read
Group 40 Variation 2
16bit Analog with flag
Direct Operate
Group 41 Variation 2
16bit Analog with flag
Direct Op Value
0
Analog
1
Digital Input Alarm if < 1v
2
Digital Input Alarm if > 2v
Low Capacity Alarm
3
Digital Out NC
4
Digital Out NO