BTRM Battery Test Remote Monitoring System – User Guide V3.2 |
ã
2021 Ventev | LIT SKU: 09834
13
7.1.4
Load Current
This is the measurement of the battery current.
Positive Load current 0.0 to 20.0 Amps BTRM300 / 0.0 to 10.0 Amps BTRM400
7.1.5
Supply Voltage
This is the measurement of power supply voltage.
Range 0.0 to 60.0V depending on selected range.
7.1.6
System Temperature
This is the BTRM temperature in °C.
7.1.7
Capacity
This is the measurement of the battery’s capacity level.
This capacity Good/Low status reading is present after the first test is completed.
7.1.8
IO Channel 1 – Analog V
This is the measurement of the voltage present at Channel 1 (ground referenced).
Range 0.0 to 60.0V (regardless of range selected)
7.1.9
IO Channel 1 – Digital In
This is the logic setting for IO Channel 1 (see port options menu) TRUE/FALSE
7.1.10
IO Channel 1 – Digital Out
This indicates that the IO Channel 1 relay has been set to indicate a battery relate fault
(see port options menu).
OFF The relay is set for normal operation.
ON
The relay is set to indicate a battery fault as diagnosed by the BTRM.
7.1.11
IO Channel 2 – Analog V
This is the measurement of the voltage present at Channel 2 (ground referenced).
Range 0.0 to 60.0V (regardless of range selected)
7.1.12
IO Channel 2 – Digital In
This is the logic setting for IO Channel 2 (see port options menu) TRUE/FALSE
7.1.13
IO Channel 3 – Analog In
This is the measurement of the voltage present at Channel 3 (ground referenced)
Range 0.0 to 60.0V (regardless of range selected)
7.1.14
IO Channel 4 – Analog In
This is the measurement of the voltage present at Channel 4 (ground referenced)
Range 0.0 to 60.0V (regardless of range selected)
7.1.15
System Voltage Type
The type of batter voltage the system is operating at.
Not available on all modes – check the Port Options menu to confirm System Voltage
Type
7.1.16
System Up Time
The time the system has been operational.