BTRM Battery Test Remote Monitoring System – User Guide V3.2 |
ã
2021 Ventev | LIT SKU: 09834
41
13.2
Function 02 Input Status | Read Discrete Input
13.3
Function 03 Holding Registers | Read Single or Multiple
13.4
Function 04 Input Registers | Read Single or Multiple
13.5
Function 05 Boolean (Coils) | Write Discrete Output
Point
Description
State
Value
0
Low Battery Capacity
Low
0x01
1
Low Battery Voltage
Low
0x01
2
DNP3 Unsolicited Enabled
Enabled
0x01
3
Aux IO Channel 1 Digital In
Tripped
0x01
4
Aux IO Channel 2 Digital In
Tripped
0x01
5
Any Fault Flag
Tripped
0x01
Point Description
State
Value
0
Battery Minimum Runtime
Minutes
1
Battery Test Schedule Time
Hours
2
Battery Test Next Test Time
Hours
3
Aux IO Channel 1 Config
1,2,3
4
Aux IO Channel 2 Config
1,2,3,4,5
5
System Selection 12V /24V
1,2 (12v/24v)
12v/24v
Point Description
Units
0
Battery Voltage
millivolts
1
Charger Voltage
millivolts
2
Power Supply Voltage
millivolts
3
Battery Current
milliamps
4
Temperature
°C
5
Battery Minimum Runtime Minutes
6
Battery Runtime Estimate
Minutes
7
Battery Test Temperature
°C
8
Battery Test Schedule Time Hours
9
Battery Test Next Time
Hours
10 Aux IO Channel 1 Voltage
millivolts
11 Aux IO Channel 2 Voltage
millivolts
12 Firmware Version
integer
Point Description
State
Value
State
Value
0
Battery Data Reset
Write to Enable
0x01
Write to Disabled
0x00
1
Battery LV Disconnect Enable
Write to Clear
0x01
Cleared
0x00
2
Battery Test Enable
Write to Start
0x01
Write to Stop
0x00
3
Battery Start / Stop Test
Write to Start
0x01
Write to Stop
0x00