5 Connecting to power supply

VEGAPULS 64 • 4 … 20 mA/HART - two-wire

51141-EN-160815

With plastic housing, the NPT cable gland or the Conduit steel tube 

must be screwed without grease into the threaded insert.
Max. torque for all housings, see chapter "

Technical data

".

If screened cable is required, the cable screen must be connected on 

both ends to ground potential. In the sensor, the screen is connected 

directly to the internal ground terminal. The ground terminal on the 

outside of the housing must be connected to the ground potential (low 

impedance).
In Ex systems, the grounding is carried out according to the installa-

tion regulations.
In electroplating plants as well as plants for cathodic corrosion protec-

tion it must be taken into account that significant potential differences 

exist. This can lead to unacceptably high currents in the cable screen 

if it is grounded at both ends.

Information:

The metallic parts of the instrument (process fitting, sensor, concen-

tric tube, etc.) are connected with the internal and external ground 

terminal on the housing. This connection exists either directly via 

the conductive metallic parts or, in case of instruments with external 

electronics, via the screen of the special connection cable.
You can find specifications on the potential connections inside the 

instrument in chapter "

Technical data

".

5.2 Connecting

The voltage supply and signal output are connected via the spring-

loaded terminals in the housing.
Connection to the display and adjustment module or to the interface 

adapter is carried out via contact pins in the housing.

Information:

The terminal block is pluggable and can be removed from the 

electronics. To do this, lift the terminal block with a small screwdriver 

and pull it out. When reinserting the terminal block, you should hear it 

snap in.

Proceed as follows:
1.  Unscrew the housing lid
2.  If a display and adjustment module is installed, remove it by turn-

ing it slightly to the left.

3.  Loosen compression nut of the cable gland and remove blind 

plug

4.  Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 

1 cm (0.4 in) of insulation from the ends of the individual wires

5.  Insert the cable into the sensor through the cable entry

Cable screening and 

grounding

Connection technology

Connection procedure

Содержание VEGAPULS 64

Страница 1: ...Operating Instructions Radar sensor for continuous level measurement of liquids VEGAPULS 64 4 20 mA HART two wire Document ID 51141...

Страница 2: ...s 16 4 2 Mounting versions plastic horn antenna 16 4 3 Mounting preparations mounting strap 19 4 4 Mounting instructions 20 4 5 Measurement setup Flow 26 5 Connecting to power supply 5 1 Preparing the...

Страница 3: ...Software update 66 9 7 How to proceed if a repair is necessary 66 10 Dismount 10 1 Dismounting steps 67 10 2 Disposal 67 11 Supplement 11 1 Technical data 68 11 2 Radio astronomy stations 80 11 3 Dim...

Страница 4: ...personnel and put into practice by them 1 3 Symbols used Information tip note This symbol indicates helpful additional information Caution If this warning is ignored faults or malfunctions can result...

Страница 5: ...tions This is a state of the art instrument complying with all prevailing regulations and guidelines The instrument must only be operated in a technically flawless and reliable condition The operator...

Страница 6: ...for Europe The instrument was tested according to the latest issues of the har monized standards EN 302372 Tank Level Probing Radar EN 302729 Level Probing Radar It is hence approved for use inside a...

Страница 7: ...onditions This device may not cause interference and This device must accept any interference including interference that may cause undesired operation of the device This device is approved for unrest...

Страница 8: ...e done by trained installers in strict compliance with the manufacturer s instructions This device shall be installed only at fixed locations The LPR device shall not operate while being moved or whil...

Страница 9: ...s L appareil LPR ne doit pas tre utilis pendant qu il est en train d tre d plac ou se trouve dans un conteneur en mouvement Les applications portables sont interdites La vente des particuliers est int...

Страница 10: ...51141 EN 160815 tection The environment management system is certified according to DIN EN ISO 14001 Please help us fulfil this obligation by observing the environmental instructions in this manual Ch...

Страница 11: ...abel contains the serial number of the instrument With it you can find the following instrument data on our homepage Product code HTML Delivery date HTML Order specific instrument features HTML Operat...

Страница 12: ...spective scope of delivery results from the order specification 3 2 Principle of operation VEGAPULS 64 is a radar sensor for continuous level measurement of liquids The small process fittings offer pa...

Страница 13: ...ible transit damage immediately at receipt Ascertained transit damage or con cealed defects must be appropriately dealt with Up to the time of installation the packages must be left closed and stored...

Страница 14: ...ote parameter adjustment of plics sensors Adjustment is carried out via PACTware DTM and the integrated USB connection You can find further information in the supplementary instructions PLICSMOBILE T6...

Страница 15: ...dule VEGAPULS series 60 is a replacement part for radar sensors of VEGAPULS series 60 A different version is available for each type of signal output You can find further information in the operating...

Страница 16: ...um Abrasion and mechanical influences You can find detailed information on the process conditions in chapter Technical data as well as on the type label As a standard feature the VEGAPULS 64 is separa...

Страница 17: ...sensor up to 180 for optimal orientation and rotating for optimal connection Fig 3 Ceiling mounting via the mounting strap with length 300 mm As an alternative the strap mounting is carried out horizo...

Страница 18: ...is suitable for different vessel flanges DN 80 ASME 3 and JIS 80 It comes not sealed against the radar sensor and can thus only be used unpressurized It can be retrofitted on instruments with single...

Страница 19: ...al data Required tools Allen wrench size 4 There are two different variants of screwing the strap to the sensor see following illustration 1 2 Fig 8 Mounting strap for screwing to the sensor 1 For ang...

Страница 20: ...st be used for the flange screws We recommended elastic washers or detent edged rings Screw size Disc spring type Article no M16 5 8 Detent edged ring Gross VS KD 2 32880 M20 3 4 Detent edged ring Gro...

Страница 21: ...ase keep this in mind when mounting or making changes later When mounting the sensor keep a distance of at least 200 mm 7 874 in from the vessel wall If the sensor is installed in the center of dished...

Страница 22: ...uct Fig 14 Mounting of the radar sensor with inflowing medium The socket piece should be dimensioned in such a way that the an tenna end protrudes at least 5 mm 0 2 in out of the socket ca 5 mm Fig 15...

Страница 23: ...d h Fig 16 Socket mounting with deviating socket dimensions Socket diameter d Socket length h 40 mm 50 mm 150 mm 80 mm 200 mm 100 mm 300 mm 150 mm 500 mm Socket diameter d Socket length h 1 2 5 9 in 3...

Страница 24: ...50 mm 150 mm 80 mm 200 mm 100 mm 300 mm 150 mm 500 mm Socket diameter d Socket length h 2 5 9 in 3 11 8 in 4 15 8 in 6 19 7 in In liquids direct the sensor as perpendicular as possible to the prod uct...

Страница 25: ...or has a clear view to the measured product In case of existing vessel installations a false signal suppression should be carried out during setup If large vessel installations such as struts or suppo...

Страница 26: ...ormation on flow measurement Detailed planning information is available from flume manufacturers and in special literature h max 2 x h max 90 4 3 4 hmax 90 2 3 1 Fig 23 Flow measurement with rectangul...

Страница 27: ...hmax 1 B Fig 24 Flow measurement with Khafagi Venturi flume hmax max filling of the flume B tightest constriction in the flume 1 Position sensor 2 Venturi flume In general the following points must be...

Страница 28: ...apter Technical data The instrument is connected with standard two wire cable without screen If electromagnetic interference is expected which is above the test values of EN 61326 1 for industrial are...

Страница 29: ...terminal on the housing This connection exists either directly via the conductive metallic parts or in case of instruments with external electronics via the screen of the special connection cable You...

Страница 30: ...insert ed directly into the terminal openings In case of flexible cores without end sleeves press the terminal from above with a small screwdriver the terminal opening is then free When the screwdriv...

Страница 31: ...5 1 2 6 7 8 4 20mA 2 3 4 1 Fig 27 Electronics and terminal compartment single chamber housing 1 Voltage supply signal output 2 For display and adjustment module or interface adapter 3 For external dis...

Страница 32: ...cted connection cable 1 brown and blue to power supply or to the processing system 2 Shielding 5 6 Switch on phase After connecting the instrument to power supply or after a voltage recurrence the ins...

Страница 33: ...ed by 90 It is not necessary to interrupt the power supply Proceed as follows 1 Unscrew the housing lid 2 Place the display and adjustment module on the electronics in the desired position and turn it...

Страница 34: ...chamber housing 1 In the electronics compartment 2 In the terminal compartment Note If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indicat...

Страница 35: ...sition changes continuously When the OK and ESC keys are pressed simultaneously for more than 5 s the display returns to the main menu The menu language is then switched over to English Approx 60 minu...

Страница 36: ...the measured value indication is carried out through the or ESC keys or automatically after 3 s You can find Extended adjustment in the next sub chapter 6 5 Parameter adjustment Extended adjustment Th...

Страница 37: ...comprises Capital letters from A Z Numbers from 0 9 Special characters _ blanks In this menu item you select the distance unit and the temperature unit For the distance units you can choose between m...

Страница 38: ...y to sporadic false echoes Stable and reliable measured values through averaging High accuracy because not set for max speed False signal suppression recommended Storage tank on ships Cargo Tank Mediu...

Страница 39: ...t can go through the bot tom Process measurement conditions Condensation on the plastic ceiling In outdoor facilities water and snow on vessel top possible Properties sensor False signals outside the...

Страница 40: ...measured values through frequent averag ing Insensitive in the close range Rain water spillover weir Rate of level change slow level change Process measurement conditions Ice and condensation on the a...

Страница 41: ...he ESC and the key Caution If liquids with different dielectric constants separate in the vessel for example through condensation the radar sensor can detect under certain circumstances only the mediu...

Страница 42: ...an find specifications on the reference plane in chapter Technical data The actual level is calculated on the basis of these settings The actual product level during this adjustment is not important b...

Страница 43: ...ntage value with and save with OK The cursor jumps now to the distance value 4 Enter the suitable distance value in m for the empty vessel e g distance from the sensor to the vessel bottom correspondi...

Страница 44: ...ble without entering a PIN Select menu items and show data Read data from the sensor into the display and adjustment mod ule Releasing the sensor adjustment is also possible in any menu item by enteri...

Страница 45: ...hnical data In delivery status the lighting is switched on In this menu item the device status is displayed The min and max measured value the measurement certainty as well as the min and max electron...

Страница 46: ...tion During simulation the simulated value is outputted as 4 20 mA cur rent value and as digital HART signal The status message within the context of the asset management function is Maintenance To de...

Страница 47: ...out by the user are reset to the default values see below table Proceed as follows 1 Select with under Additional adjustments the menu item Reset and confirm with OK 2 Confirm with OK and select the r...

Страница 48: ...strument Menu Menu item Default value Setup Measurement loop name Sensor Units Distance in m Temperature in C Application Medium Water solution Application Storage tank Vessel top Dished form Vessel b...

Страница 49: ...e written into one or more sen sors or kept as backup for a possible electronics exchange Note Before the data are saved in the sensor a safety check is carried out to determine if the data match the...

Страница 50: ...etected Proceed as follows 1 Select with the menu item False signal suppression and confirm with OK 2 Confirm again with OK 3 Confirm again with OK 4 Confirm again with OK and enter the actual distanc...

Страница 51: ...n curves are preprogrammed for these vessels They represent the correlation between the level percentage and vessel volume The linearization applies to the measured value indication and the current ou...

Страница 52: ...a display and adjustment module the data in the sensor can be saved in the display and adjustment module The procedure is described in the menu Additional adjust ments in the menu item Copy device set...

Страница 53: ...ignal cable 1 Sensor 2 HART resistance 250 optional depending on evaluation 3 Connection cable with 2 mm pins and terminals 4 Processing system PLC Voltage supply 5 Interface adapter for example VEGAC...

Страница 54: ...t DTM Collection Furthermore not all described functions are included in older firmware versions You can download the latest instrument software from our homepage A description of the update procedure...

Страница 55: ...k calculation program as well as a multiviewer for display and analysis of the saved measured value and echo curves The standard version is available as a download under www vega com downloads and Sof...

Страница 56: ...2 Field Communicator 375 475 Device descriptions for the instrument are available as EDD for pa rameter adjustment with the Field Communicator 375 or 475 For the integration of the EDD in the Field C...

Страница 57: ...temperature When the instrument is shipped the measured value memory is active and stores distance measurement certainty and electronics temperature every 3 minutes The requested values and recording...

Страница 58: ...pecification Maintenance requirement and explained by pictographs 4 1 2 3 Fig 38 Pictographs of the status messages 1 Failure red 2 Out of specification yellow 3 Function check orange 4 Maintenance bl...

Страница 59: ...ifference between min and max 10 mm Bit 1 of Byte 0 5 F025 Error in the linearization table Index markers are not continuously rising for example illogical value pairs Check linearization table Delete...

Страница 60: ...instrument with bigger measuring range Bit 10 of Byte 0 5 F265 Measurement function dis turbed Sensor no longer carries out a measurement Operating voltage too low Check operating voltage Carry out a...

Страница 61: ...M501 Error in the non active lin earization table Hardware error EEPROM Exchanging the elec tronics Send instrument for repair Bit 1 of Byte 14 24 M502 Error in the event memory Hardware error EEPROM...

Страница 62: ...iminate them Error Cause Rectification 4 20 mA signal not sta ble Fluctuations of the measured variable Set damping appropriate to the instrument via the display and adjustment module or PACTware DTM...

Страница 63: ...ipe hence running time error small measurement error close to 100 large error close to 0 Check parameter Application with respect to vessel form adapt if necessary bypass standpipe diameter 2 Measured...

Страница 64: ...l time 0 Amplitude of a multiple echo vessel top product surface is larger than the level echo Check parameter Application especially vessel top type of medium dished bottom high dielectric constant a...

Страница 65: ...l suppression in the close range by editing With bulk solids use radar sen sor with purging air connection Depending on the reason for the fault and the measures taken the steps described in chapter S...

Страница 66: ...ware Current instrument software as file You can find the current instrument software as well as detailed information on the procedure in the download area of our homepage www vega com Caution Instrum...

Страница 67: ...companies We use recyclable materials and have designed the parts to be easily separable Correct disposal avoids negative effects on humans and the environ ment and ensures recycling of useful raw mat...

Страница 68: ...th integrated antenna Process fitting 316L Antenna PEEK seal antenna system FKM FFKM Process seal Klingersil C 4400 Flange with encapsulated antenna system Flange 316L Flange plating PTFE Antenna enca...

Страница 69: ...5 lbf ft Max torques plastic horn antenna Mounting screws mounting strap on sensor housing 4 Nm 2 950 lbf ft Flange screws compression flange DN 80 5 Nm 3 689 lbf ft Flange screws adapter flange DN 1...

Страница 70: ...to 20 m 65 62 ft Plastic horn antenna up to 30 m 98 43 ft Flange with encapsulated antenna system DN 50 2 up to 25 m 82 02 ft Flange with encapsulated antenna system from DN 80 3 up to 30 m 98 43 ft...

Страница 71: ...cording to DIN EN 61298 1 Temperature 18 30 C 64 86 F Relative humidity 45 75 Air pressure 860 1060 mbar 86 106 kPa 12 5 15 4 psig Installation reference conditions Min distance to internal installati...

Страница 72: ...apsulated antenna system 1 Reference plane 2 Antenna edge 3 Recommended measuring range Repeatability 1 mm Deviation with bulk solids The values depend to a great extent on the application Binding spe...

Страница 73: ...1 m 3 W cm Ambient conditions Ambient storage and transport tempera ture 40 80 C 40 176 F Process conditions For the process conditions please also note the specifications on the type label The lowest...

Страница 74: ...enic fitting with encapsulated anten na system PTFE PTFE 40 130 C 40 266 F FKM A P 75 5 VA 75F 20 130 C 4 266 F EPDM A P 75 5 KW75F 40 130 C 40 266 F FFKM Kalrez 6375 15 130 C 5 266 F Ambient temperat...

Страница 75: ...t temperature Process temperature thread G and G1 with integrated horn antenna up to 200 C 392 F A Ambient temperature B Process temperature 1 Aluminium housing 2 Plastic housing 3 Stainless steel hou...

Страница 76: ...Aluminium housing 2 Plastic housing 3 Stainless steel housing precision casting 4 Stainless steel housing electropolished 0 C 32 F 40 C 40 F 80 C 176 F 57 C 135 F 60 C 140 F 52 C 126 F 67 C 159 F 200...

Страница 77: ...rding to EN 60068 2 6 vibration with resonance with mounting strap 1 g at 5 200 Hz according to EN 60068 2 6 vibration with resonance Vibration resistance Thread with integrated horn antenna flange wi...

Страница 78: ...rt Cable diameter 4 5 8 5 mm 5 9 mm 6 12 mm 7 12 mm 10 14 mm PA NBR Brass nickel plated NBR Stainless steel NBR Wire cross section spring loaded terminals Massive wire stranded wire 0 2 2 5 mm AWG 24...

Страница 79: ...nt unit Data transmission Digital I C Bus Connection cable Four wire Sensor version Configuration connection cable Cable length max Standard cable Special cable Screened 4 20 mA HART 50 m Integrated c...

Страница 80: ...ar IP 68 1 bar Type 6P Stainless steel electro polished Single chamber IP 66 IP 68 0 2 bar Type 6P Stainless steel precision casting Single chamber IP 66 IP 68 0 2 bar IP 68 1 bar Type 6P Double chamb...

Страница 81: ...8 N 03 23 34 W Sweden Onsala 57 23 45 N 11 55 35 E 11 3 Dimensions The following dimensional drawings represent only an extract of all possible versions Detailed dimensional drawings can be downloaded...

Страница 82: ...display and adjustment module the housing is 9 mm 0 35 in higher 1 Single chamber version 2 Double chamber version Aluminium housing with protection rating IP 66 IP 68 1 bar 120 mm 4 72 105 mm 4 13 1...

Страница 83: ...amber version electropolished 2 Single chamber version precision casting 3 Double chamber version precision casting Stainless steel housing with protection rating IP 66 IP 68 1 bar 117 mm 4 61 103 mm...

Страница 84: ...VEGAPULS 64 plastic horn antenna with compression flange 126 mm 4 96 10 5 mm 0 41 19 mm 0 75 75 mm 2 95 115 mm 4 53 156 mm 6 14 200 mm 7 87 21 mm 0 83 107 mm 4 21 1 Fig 67 Radar sensor with compressi...

Страница 85: ...flange and rinsing connection 126 mm 4 96 14 7 mm 0 58 10 5 mm 0 41 26 5 mm 1 04 19 mm 0 75 75 mm 2 95 156 mm 6 14 200 mm 7 87 21 mm 0 83 107 mm 4 21 1 2 3 Fig 68 Radar sensor with compression flange...

Страница 86: ...51141 EN 160815 VEGAPULS 64 plastic horn antenna with adapter flange 2 1 144 mm 5 67 36 5 mm 1 44 20 mm 0 79 17 5 mm 0 69 75 mm 2 95 98 mm 3 86 180 mm 7 09 220 mm 8 66 Fig 69 Radar sensor with adapter...

Страница 87: ...ic horn antenna mit adapter flange und rinsing connection 3 2 1 170 mm 6 69 62 5 mm 2 46 20 mm 0 79 34 7 mm 1 37 75 mm 2 95 98 mm 3 86 180 mm 7 09 220 mm 8 66 Fig 70 VEGAPULS 64 adapter flange and rin...

Страница 88: ...n antenna with mounting strap 125 mm 4 92 2 5 mm 0 10 75 mm 2 95 107 mm 4 21 115 mm 4 53 300 mm 11 81 19 mm 0 75 98 mm 3 86 6 mm 0 24 8 5 mm 0 34 9 mm 0 35 85 mm 3 35 12 mm 0 47 9 mm 0 35 12 mm 0 47 1...

Страница 89: ...m 2 40 24 mm 0 94 SW 36 mm 1 42 G TB 25 mm 0 98 61 mm 2 40 24 mm 0 94 SW 36 mm 1 42 NPT G1 101 mm 3 98 33 mm 1 31 42 5 mm 1 67 42 5 mm 1 67 1 NPT SW 55 mm 2 17 101 mm 3 98 33 mm 1 31 SW 55 mm 2 17 TC...

Страница 90: ...3 50 19 mm 0 75 45 mm 1 77 102 mm 4 02 19 mm 0 75 Fig 73 VEGAPULS 64 encapsulated antenna system DN 50 1 Version up to 130 C 266 F 2 Version up to 200 C 392 F 181 mm 7 13 129 mm 5 08 32 mm 1 25 75 mm...

Страница 91: ...6 32 mm 1 25 40 mm 1 57 89 8 mm 3 53 79 mm 3 12 106 mm 4 17 19 mm 0 75 69 9 mm 2 75 45 mm 1 77 68 5 mm 2 70 Rd 110x1 6 Rd 78x1 6 40 mm 1 57 32 mm 1 25 97 mm 3 82 75 mm 2 95 99 mm 3 91 40 mm 1 57 CE RA...

Страница 92: ...mm 2 76 45 mm 1 77 65 mm 2 56 Rd 70 x 1 6 Q1 19 mm 0 75 70 mm 2 76 45 mm 1 77 40 mm 1 57 40 mm 1 57 40 mm 1 57 65 mm 2 56 58 mm 2 30 31 mm 1 23 50 mm 1 97 40 mm 1 57 53 mm 2 09 36 mm 1 41 50 mm 1 97 9...

Страница 93: ...tenna system 3 LA 19 mm 0 75 69 mm 2 72 23 mm 0 91 52 mm 2 03 40 mm 1 57 19 mm 0 75 69 mm 2 72 39 mm 1 54 52 mm 2 03 40 mm 1 57 90 mm 3 54 LB Fig 77 VEGAPULS 64 hygienic fitting with encapsulated ante...

Страница 94: ...ionen unter www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA linea...

Страница 95: ...memory 57 F False signal suppression 50 Fault rectification 62 Flow measurement 26 27 Foam generation 26 Functional principle 12 G Gas tight leadthrough Second Line of Defense 16 Grounding 29 H HART...

Страница 96: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Отзывы: