36
6 Set up with the display and adjustment module
VEGAPULS 64 • 4 … 20 mA/HART - two-wire
51141-EN-160815
This menu item is used to select the national language for further pa-
rameter adjustment. You can change the selection via the menu item
"
Setup - Display, Menu language
".
With the "
OK
" key you move to the main menu.
6.4 Parameter adjustment - Quick setup
To quickly and easily adapt the sensor to the application, select
the menu item "
Quick setup
" in the start graphic on the display and
adjustment module.
Select the individual steps with the
[->]
key.
After the last step, "
Quick setup terminated successfully
" is displayed
briefly.
Information:
The echo curve of setup is stored automatically during the quick
setup.
The return to the measured value indication is carried out through the
[->]
or
[ESC]
keys or automatically after 3 s
You can find "
Extended adjustment
" in the next sub-chapter.
6.5 Parameter adjustment - Extended adjustment
The main menu is divided into five sections with the following func-
tions:
Setup:
Settings, e.g., for measurement loop name, units, application,
adjustment, signal output
Display:
Settings, e.g., for language, measured value display, lighting
Diagnosis:
Information, for example, on device status, peak value,
simulation, echo curve
Additional adjustments:
Date/Time, reset, copy function, scaling,
current output, false signal suppression, linearization, HART mode,
special parameters
Info:
Instrument name, hardware and software version, calibration
date, instrument features
In the main menu item "
Setup
", the individual submenu items
should be selected one after the other and provided with the correct
Selection of national
language
Main menu