6 Set up with the display and adjustment module
VEGAPULS 64 • 4 … 20 mA/HART - two-wire
51141-EN-160815
The selected curve is continuously updated. A submenu with zoom
functions is opened with the
[OK]
key:
•
"X-Zoom": Zoom function for the meas. distance
•
"Y-Zoom": 1, 2, 5 and 10x signal magnification in "
dB
"
•
"Unzoom": Reset the presentation to the nominal measuring range
without magnification
In this menu item you can simulate measured values via the current
output. This allows the signal path to be tested, e.g. through down-
stream indicating instruments or the input card of the control system.
Select the requested simulation variable and set the requested value.
Caution:
During simulation, the simulated value is outputted as 4 … 20 mA cur-
rent value and as digital HART signal. The status message within the
context of the asset management function is "
Maintenance
".
To deactivate the simulation, you have to push the
[ESC]
key and
confirm the message
with the
[OK]
key.
Information:
The sensor terminates the simulation automatically after 60 minutes.
The function "
Setup
" allows the echo curve to be saved at the time of
setup.
Information:
This is generally recommended, however, for use of the Asset
Management functions it is absolutely necessary. Saving should be
carried out with a very low level.
The function "
Echo curve memory
" allows up to ten individual echo
curves to be stored, for example to detect the measurement behav-
iour of the sensor in different operating conditions.
Diagnosis - Simulation
Diagnostics - Echo curve
memory