48
6 Set up with the display and adjustment module
VEGAPULS 64 • 4 … 20 mA/HART - two-wire
51141-EN-160815
well as measured value and echo curve memory is deleted. The event
and parameter modification memories remain unaffected.
Basic settings:
Resets the parameter settings, incl. special param-
eters, to the default values of the respective instrument. Any stored
false signal suppression or user programmable linearisation curve, as
well as the measured value memory, is deleted. Order-related settings
are not taken over into the current parameters after this reset.
The following table shows the scope of the reset function and the
default values of the instrument:
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Units
Distance in m
Temperature in °C
Application
Medium: Water solution
Application: Storage tank
Vessel top: Dished form
Vessel bottom: Dished form
Vessel height/Measuring range: 30 m
Min. adjustment
30 m
Max. adjustment
0,000 m(d)
Damping
0.0 s
Current output
mode
Output characteristics: 4 … 20 mA
Failure mode: < 3.6 mA ▼
Current output
Min./Max.
Min. current: 3.8 mA
Max. current: 20.5 mA
Display
Displayed value 1 Filling height
Displayed value 2 Electronics temperature
Backlight
Switched on
Additional adjust-
ments
Date/Time
Time format: 24 h
Scaling size
Volume
l
Scaling format
100.00 lin %, 100 l
0.00 lin %, 0 l
Current output 1
and 2 size
Lin %
Current output 1
and 2 adjustment
100.00 %, 100 l
0.00 %, 0 l
Linearization
Linear
HART mode
HART address: 0
Loop current mode: Analogue cur-
rent output