7 Set up with the display and adjustment module
VEGABAR 86 • Secondary Device for electronic differential pressure
48048-EN-220817
Menu item
Parameter
Default setting
Adjustment
(SIL)
Distance (with density
and interface)
1.00 m
Zero/Min. adjustment
0.00 bar
0.00 %
Span/Max. adjustment
Nominal measuring range in bar
100.00 %
Damping (SIL) Integration time
0.0 s
Linearization
(SIL)
Linear, cylindrical tank,
… user-defined
Linear
Current output
(SIL)
Current output - Mode
Output characteristics
4 … 20 mA
Reaction when malfunctions oc-
cur
≤ 3.6 mA
Current output - Min./
Max.
3.8 mA
20.5 mA
Lock adjust-
ment (SIL)
Blocked, released
Last setting
Display
Menu item
Default value
Menu language
Selected language
Displayed value 1
Pressure
Displayed value 2
Ceramic measuring cell: Measuring cell temperature in °C
Metallic measuring cell: Electronics temperature in °C
Display format
Number of positions after the decimal point, automatically
Backlight
Switched on
Menu item
Parameter
Default setting
Device status
-
Peak indicator
Pressure
Current pressure measured value
Peak indicator
temp.
Temperature
Actual measuring cell and elec-
tronic temperature
Simulation
-
Menu item
Parameter
Default setting
PIN
0000
Date/Time
Actual date/Actual time
Display
Diagnostics
Additional adjustments