7 Set up with the display and adjustment module
VEGABAR 86 • Secondary Device for electronic differential pressure
48048-EN-220817
2. Edit the percentage value with
[OK]
and set the cursor to the
requested position with
[->]
.
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the density value.
4. Enter the max. density value corresponding to the percentage
value.
The max. adjustment for density is finished.
Proceed as follows:
1. Select in the menu item "
Setup
" with
[->]
"
Adjustment
" and con-
firm with
[OK]
. Now confirm the menu item "
Distance
" with
[OK]
.
2. Edit the sensor distance with
[OK]
and set the cursor to the
requested position with
[->]
.
3. Set the distance with
[+]
and save with
[OK]
.
The adjustment of the distance is hence finished.
Proceed as follows:
1. Select the menu item "
Setup
" with
[->]
and confirm with
[OK]
.
Now select with
[->]
the menu item "
Min. adjustment
" and con-
firm with
[OK]
.
2. Edit the percentage value with
[OK]
and set the cursor to the
requested position with
[->]
.
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the height value.
4. Enter the min. height of the interface corresponding to the per-
centage value.
5. Save settings with
[OK]
and move with
[ESC]
and
[->]
to the max.
adjustment.
The min. adjustment for interface is thus finished.
Proceed as follows:
1. Select the menu item "
Setup
" with
[->]
and confirm with
[OK]
.
Now select with
[->]
the menu item "
Max. adjustment
" and con-
firm with
[OK]
.
Distance interface
Min. adjustment interface
Max. adjustment interface