7 Set up with the display and adjustment module
VEGABAR 86 • Secondary Device for electronic differential pressure
48048-EN-220817
4. Verify parameters
All safety-relevant parameters must be verified after a change:
•
SIL parameter 1: Zero adjustment
•
SIL parameter 2: Secondary on/off
•
Non-SIL parameter 1: Measured value presentation
•
Non-SIL parameter 2: Display value 1, unit of the application
•
Non-SIL parameter 3: Menu language
•
Non-SIL parameter 4: Lighting
Confirm the modified values one after the other.
If the described process of parameter adjustment was run through
completely and correctly, the instrument will be locked and hence
ready for operation.
Otherwise the instrument remains in the released and hence unsafe
condition.
Information:
As long as the VEGABAR 86 is powered, the display and adjustment
module remains in the actually set adjustment menu. An automatic,
time-controlled reset to the measured value indication is not carried
out.
7.1.2 Display
In this menu item, you define which measured value is displayed.
The default setting for the displayed value is "
Differential pressure
".
In this menu item you define the number of decimal positions with
which the measured value is displayed.
The default setting for the display format is "
Automatic
".
Display value 1 and 2 -
4 … 20 mA
Display format 1 and 2