Figure 10 provides the full menu of features that can be set up on the system. Explanation of each 
feature is provided in the section “CONTROLLER FEATURES”.

When setting up the VECTOR system via the LCD display, all the steps that have to be followed are 

clearly provided via the display. It is only necessary to note the following:

?

To get into setup mode, press the (oblong) button for 3 seconds and follow the instructions 
provided from there.

?

The buttons provided on the controller for navigating the system, are not marked because at each 
step during the setup, the function given to each button is provided on the display.

?

When not in setup mode, ie normal mode, the (round) button is used as a TEST button for 
operating the system. The up/down buttons are not used unless the diagnostic screens have been 
selected to appear in normal mode, in which case these buttons allow switching from one screen 
to the next.

For each feature a factory default setting has been programmed into the controller. Referred to as 
an operating standard or PROFILE, these defaults have been determined to suit the requirements 
of the specific region where the installation is being carried out. It is only necessary to change a 
feature where the default does not suit the installation. When selecting any feature in the menu, 
details of the current setting stored in the controller are displayed. 

Refer to Table 1 on page 39 for the Schedule of Factory Defaults for each feature

Page 28

Menu Navigation Map

Menu Navigation Map

Page 29

Figure 10 Part A of “Menu Navigation Map”

Figure 9 View of Controller

SETTING LIMITS: 1

SAFETY: 2

AUTOCLOSE: 3

MODES OF OPERATION: 4

RUN PROFILE: 5

IR BEAMS: 6

Setup Wizard

MTRM Collision Force: 2.1

MTRS Collision Force: 2.2

Collision Count: 2.3

Autoclose Status: 3.1

Autoclose Time: 3.2

Autoclose Override Time: 3.3

Autoclose Advanced Options: 3.4

Operating Mode

Positive Close: 5.1

Leaf Delay: 5.2

Pre-Open Delay: 5.3

Pre-Close Delay: 5.4

Opening Speed: 5.5

Closing Speed: 5.6

Ramp up Distance: 5.7

Ramp down Distance: 5.8

Crawl Distance: 5.9

Torque Limit: 5.10

MTRM Opening Collision Force

MTRM Closing Collision Force

MTRS Opening Collision Force

MTRS Closing Collision Force

Autoclose on Open: 3.4.1

Autoclose on Partly Open: 3.4.2

Autoclose on Partly Closed: 3.4.3

Standard Mode

Condominium Mode

Reversing Mode

Positive Close Status: 5.1.1

Positive Close Type: 5.1.2

Positive Close Short Stop Value: 5.1.3

Positive Close Push Force: 5.1.4

Leaf Delay Status: 5.2.1

Leaf Delay Value: 5.2.2

Short Stop

MTRM Only

MTRS Only

MTRM & MTRS

PIRAC Control: 6.1

SAF Output Status: 6.2

IRBO = IRBC

IR Beam Alarms: 6.3

PIRAC Status: 6.1.1

Stop On Open: 6.1.2

Ambush Alarm: 6.3.1

Break in Alarm Status: 6.3.2

Stop On Open Status: 6.1.2.1

Stop Distance: 6.1.2.2

Ambush Alarm Status: 6.3.1.1

IRB Broken time: 6.3.1.2

S Sens1
S Sens2
M Sens1
M Sens2
Sens+
Sens-

Safe CLS
Safe OPN
Com
LCK/STP

TRG
PED
Com
FRX
LIT

Figure 10 provides the full menu of features that can be set up on the system. Explanation of each 
feature is provided in the section “CONTROLLER FEATURES”.

When setting up the VECTOR system via the LCD display, all the steps that have to be followed are 

clearly provided via the display. It is only necessary to note the following:

?

To get into setup mode, press the (oblong) button for 3 seconds and follow the instructions 
provided from there.

?

The buttons provided on the controller for navigating the system, are not marked because at each 
step during the setup, the function given to each button is provided on the display.

?

When not in setup mode, ie normal mode, the (round) button is used as a TEST button for 
operating the system. The up/down buttons are not used unless the diagnostic screens have been 
selected to appear in normal mode, in which case these buttons allow switching from one screen 
to the next.

For each feature a factory default setting has been programmed into the controller. Referred to as 
an operating standard or PROFILE, these defaults have been determined to suit the requirements 
of the specific region where the installation is being carried out. It is only necessary to change a 
feature where the default does not suit the installation. When selecting any feature in the menu, 
details of the current setting stored in the controller are displayed. 

Refer to Table 1 on page 39 for the Schedule of Factory Defaults for each feature

3

3

3

3

3

Exit

Go

Up/Dn

Exit

Go

Up/Dn

Exit

Go

Up/Dn

Exit

Go

Up/Dn

Exit

Go

Up/Dn

Exit

Go

Up/Dn

Exit

Go

Up/Dn

Exit

Go

Up/Dn

Exit

Go

Up/Dn

AutoClose

AutoClose

AutoClose

AutoClose

AutoClose

Menu Level

Menu Level

How to set up additional features
on the Vector Controller

How to set up additional features
on the Vector Controller

Содержание V400

Страница 1: ...otech Group Pty T 07 3205 1123 F 07 3205 1124 E info rotech com au...

Страница 2: ...ing gates 24 Electrical Set up 26 Control box Installation 26 Additional Features 28 Menu navigation map 29 Controller Features 31 Factory Defaults Schedule 39 Description of terminal functions 41 LED...

Страница 3: ...se this gate and be sure that they near the gate area understand the hazards associated with automated gates 6 Secure all easily accessed gate opener controls in order to preventunauthorizeduse of the...

Страница 4: ...for sensitive edges or beams on both the closing and opening directions of the gate Advanced closed loop speed control to maintain safe and reliable operation on inclined gates under windy conditions...

Страница 5: ...d 400mm Stroke 400mm Stroke Model V400 100 95mm All dimensions shown in millimetres Model V500 1600mm Extended 1600mm Extended 1100mm Retracted 1100mm Retracted 100 95mm All dimensions shown in millim...

Страница 6: ...0kgf 200 V400 14 Sec V500 17 5 Sec V400 5 5kg V500 5 9kg V400 400mm V500 500mm 20 C to 60 C IP55 7AH 12V CP84E Domestic 7AH 12V CP84SM2A Light Industrial Standby period day 1 day 2 days Double kit inc...

Страница 7: ...g 750kg 750kg 550kg 410kg 310kg 100 750kg 750kg 600kg 420kg 310kg 230kg 110 750kg 500kg 320kg 220kg 120 310kg 170kg 110kg 1 an electric lock must be fitted to secure gate in closed position NOT RECOMM...

Страница 8: ...operator keys 1 GTKEYTG01 8 Gate warning decal 2 LABELGATE1 9 Cap screw M6 x 25 SS 1 B124106025 10 14mm snap ring 1 F1400SNAPR 11 12mm snap ring 1 F1200SNAPR 12 M6 nut SS 1 N1202060SS Keys are specifi...

Страница 9: ...tor kit packing leaflet 1 DOC1050D06 Wall adaptor kit optional VECWAK00V1 3 1 2 4 15 7 5 1 2 7 4 5 6 3 1 2 3 4 5 6 7 1 1 1 1 1 2 1 1 1 1 1 1 VECC D00V2 CP84E V2 Misc parts DOC1050D01 1050D010009 TX4NV...

Страница 10: ...High security kit optional VECHSK00V1 Page 11 1 2 3 Item Description Qty Part No 1 Vector securing plate short 1 1050M3200D 2 Vector securing plate long 1 1050M3300D 3 M10x35 Bolt 2 B121210035 4 M10 N...

Страница 11: ...ate adaptor kit optional VECGAK00V1 1 2 3 4 Item Description Qty Part No 1 Piston guard 1 1050M0321P 2 Guard retainer 1 DOMCEN0070 3 Guard sleeve 1 DOMCEN0070 4 Guard cap 1 DOMCEN0070 5 Guard pin 1 10...

Страница 12: ...ers Side Cutters Hammer 2 X G Clamps Electric Drilling Machine Measuring Tape Hacksaw Angle Grinder Spirit Level Marking pen Chalk 5mm Allen Key 20mm Hole Saw Connector block Safety Equipment Goggles...

Страница 13: ...ght domestic gates that are about 1 5m long and that is mounted on pillars of average strength This mounting is highly recommended for all light industrial gates or for heavy gates of any length Alter...

Страница 14: ...fitting VECTORS to existing installations and also makes adjustments easier when doing new installations Applications Light industrial Heavy gates Frequent use Applications Domestic Medium gates Freq...

Страница 15: ...in the required open position See diagram below 4 Check the strength of the mounting pillar and fit a wall adaptor kit where needed 5 If the swing gate leaf is longer than 2 5m ensure that a lock can...

Страница 16: ...ric lock 2 core 0 5mm note 4 Optional radio receiver cable 3 core 9 Optional pillar light cable 3 core size 2 0 5mm multi stranded optional according to power reg 5 Optional pedestrian key switch 2 co...

Страница 17: ...t the bracket according to A and B values in the tables on pages 23 and 25 B A 120 110 100 90 80 70 60 Gate opening angle 0 120 110 100 90 80 70 60 Gate opening angle 0 For tables see page 23 or 25 or...

Страница 18: ...erator 1 OR 2 TURNS 6 Fit the motor end of the operator to the wall bracket 7 Open the gate fully and temporarily clamp the gate bracketto the gate Determine the gate bracket position Page 19 The gate...

Страница 19: ...it operator wall bracketpins and snap rings Fasten gate bracket to gate Page 20 See page 14 for site considerations If it becomes obvious that the operator does not have enough stroke reduce either th...

Страница 20: ...cure in place with an allen key tighten properly 15 Attach warningdecals to the gate as shown 2 1 Adjust origin clamp NB Not required for outward swinging gates Page 21 open 12 Fit operator gate brack...

Страница 21: ...ight angles to the centre line of thegateinitsopenposition Ensure that the gate does not exceed the gatemassspecificationsonpage8 For best security but slower operation installwithlargeBvalue For fast...

Страница 22: ...0 120 110 110 120 100 110 90 80 70 60 Gate opening angle 0 120 100 110 90 80 70 60 Gate opening angle 0 1400mm Extended 1400mm Extended 1000mm Retracted 1000mm Retracted 1600mm Extended 1600mm Extende...

Страница 23: ...ificationsonpage8 Outward opening swing gates must have physical end stops fitted in the open position OriginclampsmustNOTbefitted For best security but slower operation installwithlargeBvalue For fas...

Страница 24: ...0 120 130 120 106 114 120 100 110 90 80 70 60 Gate opening angle 0 120 100 110 90 80 70 60 Gate opening angle 0 1400mm Extended 1400mm Extended 1000mm Retracted 1000mm Retracted 1600mm Extended 1600mm...

Страница 25: ...er housing it is recommended to mount a small junction box adjacent each operator Terminate the cable provided on the operator into this junction box and then route a new cable from the junction box t...

Страница 26: ...Dn Exit Go Up Dn Exit Go Up Dn AutoClose AutoClose AutoClose AutoClose AutoClose 9 If powering up the system ex factory it will request for the operating PROFILE operating standard to be set Select fr...

Страница 27: ...Figure 10 provides the full menu of features that can be set up on the system Explanation of each feature is provided in the section CONTROLLER FEATURES When setting up the VECTOR system via the LCD...

Страница 28: ...9 Torque Limit 5 10 MTRM Opening Collision Force MTRM Closing Collision Force MTRS Opening Collision Force MTRS Closing Collision Force Autoclose on Open 3 4 1 Autoclose on Partly Open 3 4 2 Autoclos...

Страница 29: ...10 2 Diagnostic Screen Status 10 3 Test Button Disabled Status 10 4 Press Master Button If menu locked ADD Remotes 11 1 DELETE Remotes 11 2 EDIT Remotes 11 3 Remotes Menu Locked Status 11 4 Courtesy...

Страница 30: ...ision fault indication will continue to flash indefinitely or until a valid trigger has been received AUTO CLOSE MENU 3 AUTO CLOSE STATUS The Auto close feature when turned on has the function of auto...

Страница 31: ...VERSING MODE A trigger impulse on TRG will reverse the direction of a moving gate If it were closing it will stop and immediately begin opening If it were opening it will stop and immediately begin cl...

Страница 32: ...re details This setting applies to both motors PRE CLOSE DELAY Allows a delay between a valid trigger signal being received and the gate commencing movement in the closing direction The delay will als...

Страница 33: ...ed and stop if they are opening Two independent normally closed inputs are provided for opening and closing safety beams An interrupted closing beam will prevent the gates from closing and stop and re...

Страница 34: ...ed while the beams are broken and for a period of 30 seconds thereafter This time is fixed For example if a would be intruder is loitering at the entrance as soon as the beams are broken an alarm will...

Страница 35: ...lly closing A warning light would typically be active during this delay GATE LOCK MENU 8 An electric strike lock or magnetic lock can be connected to the control card allowing the gate to be locked wh...

Страница 36: ...ivate for the selected pre opening and pre closing delay The manner of activation is dependent on the pre flashing mode selected Mode A will turn on the courtesy light only while the motors are runnin...

Страница 37: ...cated by the system to each respective transmitter and the person to whom the transmitter is given This is necessary should selective deletion be required at a later stage DELETE REMOTES Transmitters...

Страница 38: ...Partly Closed YES NO mm ss S R C Level YES NO YES NO Level M S M S SS mm Level mm Level A Collisions B C P S L s 00 00 1 NO NO 1 1 1 1 1 3 0 1 Max 6 YES YES Max 6 Max 6 40 Max 6 15 255 2 0 15 Standard...

Страница 39: ...me IRBO acts as IRBC IRB Alarms Output Gate Lock Location Gate Lock Drive Type PED Auto Close Time PED Pre Open Delay Time PED Pre Close Delay Time Full Open YES NO YES NO YES NO YES NO YES NO Minutes...

Страница 40: ...electronically override the Safety Inputs and allow the system to function without the links However if safeties are connected to either or both inputs thereafter there must be a normally closed circu...

Страница 41: ...nnected between 12V and SOL Note that the maximum current draw allowed for the lock is 2A Should the solenoid lock or magnetic lock exceed this current rating it is necessary to use an interposing rel...

Страница 42: ...Gate open Gate closed Signal present No signal Opening Safeties clear Opening Safeties obstructed Closing Safeties clear Closing Safeties obstructed Signal present No signal Signal present No signal S...

Страница 43: ...low 3A 250mA Fast Blow S Sens1 S Sens2 M Sens1 M Sens2 Light Light Batt Batt MTR M MTR M MTR S MTR S Sens Sens Safe CLS Safe OPN Com LCK STP TRG PED Com FRX LIT LED Com Aux 12V Safe Com Sol 220V AC Ma...

Страница 44: ...075mm 1 218mm 1 587mm 1 687mm 1 732mm 1 075mm TO 1 218mm 1 351mm 1 475mm Step 3 1m Open the gate and measure a distance along the gate a distance of 1m from the centreline of the gate hinge Make a mar...

Страница 45: ...s2 M Sens1 M Sens2 Light Light Batt Batt MTR M MTR M MTR S MTR S Sens Sens Safe CLS Safe OPN Com LCK STP TRG PED Com FRX LIT LED Com Aux 12V Safe Com Sol THIN PURPLE THIN RED GREY THICK BLUE THICK BLA...

Страница 46: ...RED BLUE BLUE PURPLE PURPLE PURPLE PURPLE BLUE BLUE S Sens1 S Sens2 M Sens1 M Sens2 Light Light Batt Batt MTR M MTR M MTR S MTR S Sens Sens Safe CLS Safe OPN Com LCK STP TRG PED Com FRX LIT LED Com Au...

Страница 47: ...B RECEIVER 12V 24V 12V or 24V IRB Tx CLOSING BEAM 12V 24V IRB RECEIVER 12V 24V 12V or 24V IRB Tx for CE compliance for CE compliance Page 48 Figure 15 Wiring diagram for safeties Wiring Diagram for Sa...

Страница 48: ...Page 49 S Sens1 S Sens2 M Sens1 M Sens2 Light Light Batt Batt MTR M MTR M MTR S MTR S Sens Sens Safe CLS Safe OPN Com LCK STP TRG PED Com FRX LIT LED Com Aux 12V Safe Com Sol...

Страница 49: ...L CIRCUITRY NEG 12V COM NC NO LOOP LOOP DETECTOR FREE EXIT CIRCUITRY HOLIDAY LOCKOUT KEYSWITCH normally CLOSED PILLAR LIGHT PUSHBUTTON normally OPEN PEDESTRIAN KEYSWITCH normally OPEN SOLENOID LED STA...

Страница 50: ...Page 51 SOLENOID OR STRIKE LOCK S Sens1 S Sens2 M Sens1 M Sens2 Light Light Batt Batt MTR M MTR M MTR S MTR S Sens Sens Safe CLS Safe OPN Com LCK STP TRG PED Com FRX LIT LED Com Aux 12V Safe Com Sol...

Страница 51: ...18 or 20 for installation details 2 an electric lock must be fitted Wind speeds for which operator will still operate the gate for V400 or V500 operators For a 100 covered gate Fully clad gates etc x...

Страница 52: ...people and objects away from the gate and its area of travel 3 NEVER LET CHILDREN OPERATE OR PLAY WITH THE GATE CONTROLS and do not allow children or pets near the gate area 4 Be careful with moving...

Отзывы: