TCI-W13, TCI-W23 Universal Controller 

O

VERVIEW

 

 

Doc: 70-00-0365, V1.0, 20200304 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

TCI-W13, TCI-W23 Series wall mounted universal controller 

 

Features 

 

Universal PI and/or binary control for any analog 

input/output signal and range 

 

Multiple auxiliary functions: heat-cool auto changeover, 

automatic enable, set point compensation 

 

Differential, averaging, min and max functions 

 

Cascading of control loops (-W23 type) 

 

Alarm monitoring of low and high limits on all inputs 

 

Programmable reaction in case of alarm 

 

Feedback function for inputs and set points 

 

Functions for dehumidifying, set point shift, cascade control 

 

Password protected programmable user and control 
parameters 

 

TCI-W23 also includes 

 

Power cap protected real-time clock with 48 hr power backup 

 

7-day programmable schedules, with options including 

change of set points and direct position of manual outputs 

 

Blue backlight 

Applications 

 

Fan coil units 

 

Heat exchangers 

 

Zoning 

 

VAV  

 

Air handlers 

 

Fan, pump control 

 

Humidifiers  

 

Dehumidifiers  

 

Ventilation  

 

Radiant heating 

 

Radiant cooling 

 

Pressurization 

General 

 

TCI-W13:  1 independent control loop, 1 internal temperature sensor, 1 universal input (analog/binary/temp), 

1 binary output, 2 analog outputs 

 

TCI-W23:  2 independent control loops, 1 internal temperature sensor, 1 universal input, 1 passive input,  

1 binary output, 2 analog outputs.  

 

Internal temperature sensor standard. Add replaceable humidity element as required or order -H version:  

AES3-HT-A2 (2%), AES3-HT-A3 (3%) or AES3-HT-A5 (5%) 

 

Flexible application configuration is made with a parameter-setting routine using the standard operation terminal 

Name 

 

Ordering 

Model 

Item code 

Loop 

Temperature 

input 

Humidity 

input 

UI  TI 

Binary 

output 

Analog 

output 

Option 

TCI-W13 

40-10 0170 

Standard 

TCI-W13-H 

40-10 0171 

RH sensor 3% acc. 

TCI-W23 

40-10 0172 

7-day programmable 

TCI-W23-H 

40-10 0173 

RH sensor 3% acc. 

AES3-HT-A2 

40-50 0102 

 

 

 

 

 

 

RH sensor 2% acc. 

AES3-HT-A3 

40-50 0103 

 

 

 

 

 

 

RH sensor 3% acc. 

AES3-HT-A5 

40-50 0104 

 

 

 

 

 

 

RH sensor 5% acc. 

Temperature sensors

: Use Vector Controls NTC sensors to achieve maximum accuracy: SDB-Tn10-20 (duct), SRA-Tn10 

(room), SDB-Tn10-20 + AMI-S10 as immersion sensor.  

Actuators

: Choose modulating actuators with an input signal type of 0

10 V DC or 4

20 mA (min. and max. signal 

limitations may be set with parameters. 3-point point actuators with constant running time are recommended).  

Binary auxiliary device

s (e.g. pumps, fans, on/off valves, humidifiers, etc.): Do not directly connect devices that 

exceed specified limits in technical specifications 

 observe startup current on inductive loads. 

 
Housing 

Blank = square housing 

In/Outputs:  

See table below

 

Control loops:  1 = 1 control loop, 2 = 2 control loops

 

Mounting:  

W = Wall mounted 

Series: 

TCI

 

T  C  I 

-  W 

Содержание TCI-W13-H

Страница 1: ...s 1 internal temperature sensor 1 universal input 1 passive input 1 binary output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required or order H version...

Страница 2: ...C 212 F 1 K Humidity Sensor AES3 HT Ax Range Measuring Accuracy Hysteresis Repeatability Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog output Output s...

Страница 3: ...or other devices Connection to voltages exceeding 42 V endangers personnel safety 88 3 5 32 1 2 21 0 8 88 3 5 Warning Live electrical components During installation testing servicing and troubleshoot...

Страница 4: ...e memorized and do not need to be re entered Upon return of power Set parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retained for...

Страница 5: ...yed clock symbol blinks Press OPTION Time schedule status displayed OFF or ON Press OPTION OFF ON blinks UP DOWN to change OPTION to save SEL PRO Pro OFF ON Creating time schedules Step 1 Select a swi...

Страница 6: ...onfiguration AO1 AO2 2 analog outputs DO Binary output configuration do1 1 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simulta...

Страница 7: ...FF OFF Celsius UP 08 Show standard display while no key is pressed ON OFF ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Set point 03 Analog output 04 Binary output 05 Clock...

Страница 8: ...passive temperature NTC or dry contact Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum...

Страница 9: ...limit in heating mode and maximum set point limit in cooling Economy mode may be disabled by setting UP06 to OFF Control loops and sequences are activated when output parameters are defined Cascade co...

Страница 10: ...This is the working range of the proportional control sequence Setting the proportional band to 0 disables proportional control Integral and differential control Proportional control is in most cases...

Страница 11: ...C 1 0 F 1L 22 Switching delay 0 255 s 10 s 1L 23 Activation of reverse direct heat cool sequence OFF activates based on demand ON follows heat cool state of controller Set manually or by auxiliary fun...

Страница 12: ...0 10 VDC default or 0 20 mA Further define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog c...

Страница 13: ...o set output to ON output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 07 Choose alarm to set output to OFF output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 08 Displ...

Страница 14: ...onds 0 1275 300 Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an out...

Страница 15: ...mit 2 ON When limit 2 is greater than limit 1 enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 16: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 17: ...0 00 0365 V1 0 20200304 Vector Controls GmbH Switzerland Page 17 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorc...