INSTALLATION
Series 65
80/129
Edition 2019-05-03
963283EA
Setup function
Command
Acknowledgement
)
Description
INTERFACE
CONFIGURATION
Set
s:20abcdefgh
s:20
Get
i:20
i:20abcdefgh
data length 8 characters
a
baud rate:
0 = 600
1 = 1200k
2 = 2400
3 = 4800
4 = 9600
5 = 19.2k
6 = 38.4k
7 = 57.6k
8 = 115.2k
b
parity bit:
0 = even
1 = odd
2 = mark
3 = space
4 = no
c
data length:
0 = 7 bit
1 = 8 bit
d
number of stop bits:
0 = 1
1 = 2
e
0 = IC
8 = PM-V2
f
digital input OPEN VALVE:
0 = not inverted
1 = inverted
2 = disabled
g
digital input CLOSE VALVE:
0 = not inverted
1 = inverted
2 = disabled
h
0 (reserved, do not change)
This function does the 0interface0 and digital input configuration.
Remark: Digital outputs are always enabled.
INTERFACE
CONFIGURATION 2
Set
s:22abbbcxxx
s:22
Get
i:22
i:22abbbcxxx
data length 8 characters
a
1 = RS485, 2 = RS485 / Point to Point
bbb
RS485 address 0...255
c
0 = full duplex, 1 = half duplex
xxx
000 (reserved, do not change)
This function defines the interface configuration for the valve.