INSTALLATION
Series 65
56/129
Edition 2019-05-03
963283EA
4.10.2.4
Pressure ramp configuration
Time Mode (Ramp Mode = Time)
Slope Mode (Ramp Mode = Slope)
The time within Target Pressure Used (ramp) reaches a
new Target Pressure is defined in parameter value
Ramp Time. Ramp Time is a value in the unit [seconds].
After setting a new Target Pressure, Target Pressure
Used will converge the Target Pressure in the slope
defines in parameter Ramp Slope. Ramp Slope is a
value in the unit [pressure / seconds]
5
7
9
11
13
15
17
19
21
0
5
10
15
p
re
ss
u
re
time
Target Pressure
Target Pressure Used (ramp)
5
7
9
11
13
15
17
19
21
0
5
10
15
p
re
ss
u
re
time
Target Pressure
Target Pressure Used (ramp)