Series 65
INSTALLATION
963283EA
Edition 2019-05-03
77/129
Setup function
Command
Acknowledgement
Description
SENSOR SCALE
Set
s:05aaaaabcd
s:05
Get
i:05
i:05aaaaabcd
data length 8 characters
a
Value
00001…99999 (10000 = 1.0000)
b
Sign Exponent
0 = “-“, 1 = “+”
c
Exponent
0…4
d
Pressure Unit
0 = Pa
1 = bar
2 = mbar
3 = ubar
4 = Torr
5 = mTorr
6 = atm
7 = psi
8 = psf
Example: 10000114 = 10Torr (input from high range sensor)
SENSOR 1
LINEARIZATION
Set
s:17aaaabbbb
s:17
Get
i:17
i:17aaaabbbb
data length 8 characters
a
logarithmic resolution[ millivolt /decade]
0000 = linearizing off
0001 = min. value
9999 = max. value
(default value: 0000 = linearizing off)
b
full scale [millivolt]
0001 = min. value
9999 = max. value
(default value in logarithmic mode: 5324 = 5.324V)
(becomes linear full scale = 1000000)
Pressure control algorithm adaptive downstream needs a linear sensor signal, therefore a
logarithmic signal must be linearized.
Example: s:1700000000 = Linear sensor
Example: s:1810007800 = Logarithmic sensor (1.0V/decade, Linear full scale at 7.8V)