INSTALLATION
Series 65
78/129
Edition 2019-05-03
963283EA
Setup function
Command
Acknowledgement
Description
SENSOR 2
LINEARIZATION
Set
s:18aaaabbbb
s:18
Get
i:18
i:18aaaabbbb
data length 8 characters
a
logarithmic resolution[ millivolt /decade]
0000 = linearizing off
0001 = min. value
9999 = max. value
(default value: 0000 = linearizing off)
b
full scale [millivolt]
0001 = min. value
9999 = max. value
(default value in logarithmic mode: 5324 = 5.324V)
(becomes linear full scale = 1000000)
Pressure control algorithm adaptive downstream needs a linear sensor signal, therefore a
logarithmic signal must be linearized.
Example: s:1700000000 = Linear sensor
Example: s:1810007800 = Logarithmic sensor (1.0V/decade, Linear full scale at 7.8V)
SENSOR AVERAGE
Set
s:19abbbbbbb
s:19
Get
i:19
i:19abbbbbbb
data length 8 characters
a
Average time
0 = 0.0 sec
1 = 0.1 sec
2 = 0.2 sec
3 = 0.3 sec
4 = 0.4 sec
5 = 0.5 sec
6 = 0.6 sec
7 = 0.7 sec
8 = 0.8 sec
9 = 0.9 sec
A = 1.0 sec
b
Reserved
set to 0000000
Remark: For pressure control averaging of sensor signal is not recommended.
This function does the sensor average configuration.