8.6.3
Current sensor
If the energy storage system to be installed is to be cascaded with
further energy storage systems, the following step will not be
carried out. Instead, see instruction manual for cascading.
(Optional add-on package required)
ATTENTION
Reversed phases!
Charging and discharging malfunction!
Conductors L1, L2, L3 for building
connection, current sensor and AC
connector must have the same phase
assignment.
Executing the connection as a right-
hand phase rotation is not sufficient!
In order to ensure the internal consumption optimisation, the
current sensor must capture all values of consumption and infeed.
Therefore, it is located directly behind the consumption and feed
meter. The current sensor is intended for top-hat rail mounting and
designed for a maximum current of 50 A per phase.