128
Subject to modification!
Updated 10/2017
11 Service and repair work
This section is intended for the qualified
electrician.
11.1
Checking the storage cabinet from outside
Is the ventilation strip on the storage cabinet cover (see Figure
1) clogged/contaminated?
The ventilation strip can be cleaned from inside once the
cover has been removed (see Chapter 11.4.7).
Is the room temperature between 5 °C and 30 °C assured
throughout the year (18 °C is the ideal temperature)?
Clarify with the customer as to how the temperature in the
installation room can be maintained. If necessary, an active fan
has to be installed.
Does the storage cabinet stand firmly?
Adjust, if necessary, using the screw feet.
Is the wall-mounting stable?
Tighten or replace the screws as necessary.
11.2
Checking the system parameters (Service)
The system parameters are checked via the web interface. To do so,
please observe Chapter 9 and the service booklet.