11.2.6 Checking the fan (Service)
From the
Settings
tab, select the
Service settings
item
.
Use
Manual fan control
to toggle between settings 0 (=
automatic), 1 (= medium setting) and 2 (= highest
setting).
Check whether the fan is blowing out air at the top. Wait
for 10 to 15 s until the fans have reached a constant
speed.
Note:
It is possible that the fans are already running.
Pay attention to noises that indicate mechanical damage.
Reset to the
Automatic
(0) setting.
To replace and clean the fan, see Chapter 11.3.7.