106
Subject to alteration!
Updated 11/2015
11.4
Completion of service and repair work
DANGER!
The battery storage system components
conduct current after a restart. .
Mortal danger from electric shock!
Once all work is complete, restore connections
and attachments to a clean condition and
check!
Make sure nobody is in the hazard zone before
connecting the power supply!
11.4.1 Checking operating state
Make sure that no contamination or material residues are
inside the device. Clean using a vacuum cleaner or
similar if necessary.
Switch the master battery module back on.
Close the door and secure with screws.
Check whether the fuses have been re-connected.
Switch on the energy storage system using the
On/Off
button. The button engages.
Check whether the LED ring indicates the following
operating states after switch on:
(1) flashes green (approx. 90 s),
(2) illuminates green (approx. 60 ) and then
(3) pulses green (= charging or discharging) or flashes
every 3 s (= standby).
Содержание element 6
Страница 1: ...INSTRUCTION MANUAL VARTA element 3 VARTA element 6 VARTA Storage GmbH ...
Страница 58: ...58 Subject to alteration Updated 11 2015 Figure 18 Installing the battery module s ...
Страница 113: ...Subject to alteration Updated 11 2015 A 1 Attachment Attachment 1a Connection diagram of the TN system ...
Страница 114: ...Subject to alteration Updated 11 2015 A 2 Attachment 1b Connection diagram of the TT system ...
Страница 115: ...Subject to alteration Updated 11 2015 A 3 Attachment 2a Connection diagram of the TN system with data logger ...
Страница 116: ...Subject to alteration Updated 11 2015 A 4 Attachment 2b Connection diagram of the TT system with data logger ...
Страница 117: ...Subject to alteration Updated 11 2015 A 5 Attachment 3a EC Declaration of Conformity VARTA element 3 ...
Страница 118: ...Subject to alteration Updated 11 2015 A 6 Attachment 4b EC Declaration of Conformity VARTA element 6 ...