11.2.7 Checking the current sensor values
Select the
System
page.
Check the current sensor values I Grid1, I Grid 2 and I
Grid 3 for plausibility:
If a current sensor value is approx. 0, although this phase
is currently loaded, the connection between current
sensor and battery storage system may be erroneously.
If necessary, load all phases separately: Switch on
selected consumers or manually discharge the battery
storage system. See chapter 9.4.3.
Note:
During a manual discharge, current from the
battery storage system is systematically applied to the
phases.
Check the current flow through all three phases, using the
current probe if necessary!
Procedures in case of unusual current sensor values:
Содержание element 6
Страница 1: ...INSTRUCTION MANUAL VARTA element 3 VARTA element 6 VARTA Storage GmbH ...
Страница 58: ...58 Subject to alteration Updated 11 2015 Figure 18 Installing the battery module s ...
Страница 113: ...Subject to alteration Updated 11 2015 A 1 Attachment Attachment 1a Connection diagram of the TN system ...
Страница 114: ...Subject to alteration Updated 11 2015 A 2 Attachment 1b Connection diagram of the TT system ...
Страница 115: ...Subject to alteration Updated 11 2015 A 3 Attachment 2a Connection diagram of the TN system with data logger ...
Страница 116: ...Subject to alteration Updated 11 2015 A 4 Attachment 2b Connection diagram of the TT system with data logger ...
Страница 117: ...Subject to alteration Updated 11 2015 A 5 Attachment 3a EC Declaration of Conformity VARTA element 3 ...
Страница 118: ...Subject to alteration Updated 11 2015 A 6 Attachment 4b EC Declaration of Conformity VARTA element 6 ...