70
Product titles
Vallox 90 MV R
Vallox 90 MV L
Product
number
3570600
3570700
HVAC code
7912066
7912067
Fans
Supply air
Extract air
0.119kW, 0.9A EC
0.119kW, 0.9A EC
Air volumes
Supply air
Extract air
73 l/s, 100Pa
84 l/s, 100Pa
Efficiencies
Annual efficiency
Supply air efficiency
Specific Fan Power (SFP)
62% B
83%
1.1 (38 l/s) B
Electrical connection
230V, 50Hz, 5.7A power
plug
Filters
Supply air
Extract air
G4 and F7
G4
Enclosure protection
class
IP34
Post-heating radiator
Electric, 900W
Heat recovery bypass
Automatic
Preheating radiator
-
Weight with packaging
52kg
Additional heating
radiator
-
Dimensions (width x
height x depth)
597x689x361mm
Input power (total) (W)
Air flow (max) (dm3/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <2.0 (kW m
3
/s)
FAN INPUT POWER
SUPPLY/EXTRACT AIR VOLUMES
TECHNICAL SPECIFICATIONS
A
B
400
350
300
250
200
150
100
50
0
0
10
20
30
40
50
60
70
80
90
100 (l/s)
0
36
72
108
144
180
216
252
288
324
360 m
3
/
h
dm
3
/s
SFP 2,0
SFP 1,5
SFP 1,0
100 %
80 %
72 %
62 %
55%
44 %
28%
11 %
Pressure loss in ducts. Total pressure (Pa)
Volume flow rate
(dm
3
/s)
A
B
11 %
28 %
44 %
55 %
62 %
72 %
80 %
100 %
0
10
20
30
40
60
70
80
90
100
50
36
72
108
0
144
180
216
252
288
324
360
dm³/s
(l/s)
m³/h
40
80
120
160
200
Sound power level in the supply air duct
by octave band L
w
, dB
Sound power level in the extract air duct
by octave band L
w
, dB
Adjustment
position
11%
28%
44%
55%
62%
72%
80%
100%
15%
11%
28%
44%
55%
62%
72%
80%
100%
15%
Air flow dm
3
/s
9.9
23.3
34.8
43.4
49.1
58.7
65.1
71.8
15.6
11.0
22.0
35.1
43.6
47.9
59.2
64.1
71.4
22.3
Air flow m
3
/h
35.6
83.9
125.3
156.2
176.8
211.3
234.4
258.5
56.16
39.6
79.2
126.4
157.0
172.4
213.1
230.8
257.0
80.28
Medium
frequency
of the
octave
band Hz
63
52.6
63.2
70.8
76.4
75.6
78.7
79.3
80.8
43.2
54.7
65.7
72.7
77.9
77.6
81.7
82.6
84.7
38.9
125
43.7
56.6
66.0
69.6
72.1
75.1
77.1
78.3
39.1
44.2
56.6
65.8
69.8
72.4
75.7
78.4
78.4
33.9
250
38.2
44.8
53.1
58.1
60.5
65.1
67.3
69.0
38.3
36.7
46.3
55.4
59.8
61.8
66.5
68.7
71.2
30.3
500
25.5
33.1
40.8
44.6
47.0
50.6
52.7
55.1
33.1
33.3
42.9
44.2
47.9
50.1
53.6
55.5
57.6
21.8
1000
21.2
33.5
39.6
43.6
45.4
48.3
50.0
51.8
27.9
24.8
34.2
40.6
43.9
45.6
48.6
49.9
51.7
19.8
2000
17.2
19.5
26.3
31.0
33.2
37.0
39.1
41.4
19.7
18.9
25.1
33.8
38.5
40.8
44.7
46.5
48.7
13.9
4000
18.6
18.9
20.4
24
25.9
29.7
32.0
34.4
17.9
18.6
19.0
24.0
28.9
31.7
36.0
38.1
40.6
18.0
8000
23.7
23.7
23.7
23.8
24.0
24.5
25.0
25.9
22.9
23.6
23.6
23.7
24.2
24.9
27.1
28.9
31.0
23.0
L
W
, dB
L
WA
, dB(A)
53.3
64.2
72.1
77.3
77.3
80.4
81.6
82.9
45.9
55.1
66.2
73.6
78.6
78.8
82.8
84.2
85.8
40.7
33.3
43.5
52.1
56.8
58.1
61.5
63.4
64.9
35.0
34.9
45.5
52.9
57.8
59.2
62.6
64.9
66.3
28.1
Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m² sound absorption)
ADJUSTMENT POSITION / AIR FLOWS (supply/extract)
Adjustment
position
100%
80%
76%
72%
62%
55%
44%
28%
11%
Air flow dm
3
/s
71.5/82.8
65.2/75.0
58.7/68.8
48.5/57.9
43.4/50.9
35.7/41.4
22.4/27.9
11.1/13.8
15.1/19.5
Air flow m
3
/h
257.4/298.1
234.7/270
211.3/247.7
174.6/208.4
156.2/183.2
128.5/149
80.6/100.4
40/49.7
54.36/70.2
L
pA
, dB (A)
43.9
41.8
40.1
38.3
34.8
30.8
27.0
25.9
24.7
SOUND VALUES
TECHNIC
AL SPECIFIC
ATIONS
extract air
supply air
Volume flow rate
Power (W)
Содержание Vallox TSK Multi 80 MV
Страница 102: ...CONFORMITY CERTIFICATES...
Страница 103: ......
Страница 104: ......
Страница 105: ...105 Vallox Oy All rights reserved...
Страница 106: ...106...
Страница 107: ...107 Vallox Oy All rights reserved...