INSTALLATION SITE
Vallox TSK Multi 50 MV and Vallox TSK Multi 80 MV
must be mounted on the ceiling. Use the mounting
hooks (4 pcs) delivered with the unit to mount the
ventilation unit on the ceiling. Observe the weight of
the unit (45 kg / 58.5 kg) when mounting.
IMPORTANT
The unit must be installed straight so that the
condensing water that collects in the bottom pool
drains through the condensing water outlet.
NOTE
Reserve a space equal to the depth of the unit in front
of the unit for servicing purposes.
NOTE
The whole length of the outdoor air duct to the unit
and exhaust air duct from the unit must be insulated
using closed cell insulation.
92
1
Ø6
1
6
INSTALLATION
MEASURING TUBES
The accessories delivered with the unit include four airflow
measuring tubes. These can be inserted in the ducts to
allow for easier ventilation adjustment.