Page 33
Installation Instructions and Owner’s Manual - L48
ENGLISH
TOP VENT HORIZONTAL TERMINAISON
One 90° Elbow
A
TO BOTTOM
OF UNIT
B
INSTALLED
VERTICALLY
1’
MINIMUM
Figure 43
Example Vent Runs
Initial Pipe
Length
A (Vertical)
B
(Horizontal)
Maximum
(Dimensions In Inches)
12
55
Natural - 24
Propane - 12
24
67
42
36
79
108 (9ft)
48
91
168 (14ft)
Note:
Pipe straps must be used every 2 feet to
secure venting.
Two 45° Elbows
B
A
Figure 44
Example Vent Runs
Initial Pipe
Length
A (Vertical)
B
(Horizontal)
Maximum
(Dimensions In Inches)
12
66
72
24
80
132 (11ft)
36
91
204 (17ft)
48
103
240 (20ft)
Two 90° Elbow
Note:
Subtract 3 feet from the total horizontal measurement for each 90° elbow installed horizontally.
Subtract 1-1/2 feet from the total horizontal measurement for each 45° elbow installed horizontally.
Figure 45
Example Vent Runs
Initial Pipe
Length
A (Vertical)
B
(Horizontal)
Maximum
(Dimensions In Inches)
12
55
0’
24
67
6
36
79
72 (6ft)
48
91
132 (11ft)