9
System errors
No. 102
Position loop (AI10) is not connected
Description
The AI10 has been selected as the position signal, but there is not connected a
potentiometer
Trouble shooting
•
Connect a potentiometer to AI10
•
Select another position signal
No. 103
Position loop (AI1) is not connected
Description
The AI1 has been selected as the position signal, but there is not connected a
potentiometer
Trouble shooting
•
Connect sensor to AI1
•
Select another position signal
No. 113
Analogue output 1 is not calibrated
Description
Analogue output 1 calibration data has not been set
Trouble shooting
•
Contact Val Controls
No. 114
Analogue output 2 is not calibrated
Description
Analogue output 2 calibration data has not been set
Trouble shooting
•
Contact Val Controls
No. 115
Pressure loop is not connected
Description
A pressure input has been selected but no sensor is detected on the input
Trouble shooting
•
Connect a pressure sensor to the input
•
Change the configuration