FST error: At 0% position
Description
The 0% switch was activated before the 100% switch was released
Trouble shooting
This error can be caused by:
•
Position sensor was disconnected
•
Position sensor is operating in the illegal area
•
Wrong configuration of the position switches
•
The valve moved from 100% directly to 0%
It can be solved by:
•
Check the position sensor
•
Make sure the position sensor is operating within the legal area
•
Check the function of the position switches