Revision: 10
47/74
8.3
Full stroke errors (451 to 468)
No. 451
FST start condition: Not at operational
Description
The valve is not at the operational position
Trouble shooting
This error can be solved by
•
Make sure the valve is at the operational position
•
Perform an endpoint calibration.
•
Increase the full stroke position deadband
No. 452
FST start condition: Low start pressure
Description
The measured pressure is below Start pressure low
Trouble shooting
This error can be solved by:
•
Increase the pressure in the hydraulic/pneumatic system
•
Decrease the Start pressure low value
No. 453
FST start condition: High start pressure
Description
The measured pressure is above Start pressure high
Trouble shooting
This error can be solved by:
•
Increase the pressure in the hydraulic/pneumatic system
•
Increase the Start pressure high value
No. 454
FST start condition: In ESD mode
Description
Emergency shutdown is detected
Trouble shooting
This error can be solved by:
•
Activate the ESD input
No. 456
Aborted by the user
Description
The test was aborted by the user
Trouble shooting
This error can be solved by:
•
Perform a new FST