DID-UM-002
Val Controls A/S
•
Limfjordsvej 3
•
DK-6715 Esbjerg N
•
Tel. +45 7547 0600
•
www.valcontrols.com
Revision: 10
6/74
4
Interface
4.1
LEDs
LED
Colour
ON
OFF
Blinking
System: Red
Red
System error
-
Calibrating
System: Green
Green
System OK
-
Initializing
ESD
Red
ESD trip
ESD normal
-
Local
Yellow
Local mode
Remote mode
-
Closed
1
Red
Valve is closed
-
Moving towards close
Open
1
Green
Valve is open
-
Moving towards open
Pump
Green
Pump is running
-
-
MT
Red
MTControl is locked
-
-
TIP
Yellow
Test in progress
-
-
Fail
Red
Last test failed
-
-
Pass
Green
Last test passed
-
-
1
) Open/close can be switched in the Interface section in ValConnect
System: Red and System: Green are the only LEDs available on the F model.
If both System: Red and System: Green is ON, the device is in bootloader mode. Power cycle the
device to return to normal operation.
4.2
MTControl
MTControl can be used to operate the AF models without opening the Ex d enclosure. It requires a
magnetic pen to “press” the buttons. The magnet must be aimed just beneath the buttons, see Figure
1. To unlock MTControl activate
→
and then
, the red MT LED will turn off if MTControl is
unlocked.
Figure 1: MTControl sensitive area