Test errors
8.1
Partial stroke errors (401 to 419)
No. 401
PST start condition: Not at operational
Description
The valve is not at the operational position
The valve must be at the operational position to perform a partial stroke. All
measured times and pressures depends on that the valve is at the end position.
Trouble shooting
This error can be solved by
•
Make sure the valve is at the operational position
•
Perform an endpoint calibration.
•
Increase the partial stroke position deadband
No. 402
PST start condition: Low start pressure
Description
The measured pressure is below Start pressure low
Trouble shooting
This error can be solved by:
•
Increase the pressure in the hydraulic/pneumatic system
•
Decrease Start pressure low
No. 403
PST start condition: High start pressure
Description
The measured pressure is above Start pressure high
Trouble shooting
This error can be solved by:
•
Decrease the pressure in the hydraulic/pneumatic system
•
Increase Start pressure high
No. 404
PST start condition: In ESD mode
Description
Emergency shutdown is detected
Trouble shooting
This error can be solved by:
•
Activate the ESD input