![Val Controls IDC24-A Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/val-controls/idc24-a/idc24-a_user-manual_849427049.webp)
DID-UM-002
Val Controls A/S
•
Limfjordsvej 3
•
DK-6715 Esbjerg N
•
Tel. +45 7547 0600
•
www.valcontrols.com
Revision: 10
49/74
No. 462
FST error: Breakaway timeout
Description
Breakaway is not detected before the Breakaway timeout was exceeded
Trouble shooting
This error may be due to:
•
Blocked output of actuator
•
Solenoid valve is stuck
This error can be solved by:
•
Clear the output of the actuator
•
Increasing the Breakaway timeout