INSTALLATION OF THE TELESCOPIC HORIZONTAL AIR/FLUE DUCT
(TOP OUTLET)
• Once the position of the flue exit
hole has been determined, the
hole should be cut through the
wall using a core drill of 125 mm
diameter.
Note: If access can be gained to
the proposed flue exit point from
outside the dwelling, the hole can
be cut with a 107 mm core drill
and the flue external wall seal
fitted from outside the dwelling.
• Measure the distance from the
outside face of the wall to the
centre of the fan outlet on the
boiler.
This is dimension A.
• Adjust the air duct and flue duct
to the lengths shown in (fig.
3.17).
• Secure the air duct sections
together by drilling a 3 mm
diameter hole through the location
hole in the end of the outer air
duct (
1
). (Ensure that the drill does
not pierce the inner flue duct).
Secure the air ducts together using
the screw (
1
) provided. Place the
adhesive tape (
2
) across the gap
in the telescopic extensions.
(fig. 3.17)
• All flue sockets should point
towards the terminal.
• Care should be taken not to
scratch the white surface of the air
duct.
• If the installation requires the use
of air/flue duct extensions,
additional bends or elbows refer
to the sections on pages 34 - 35.
1
2
*
* = 190 mm
Fig. 3.15
LAS Euro B/S 077/1
87
A
B
A
87
Fig. 3.16
LAS Euro B/S 078/0
1
2
A + 22 mm
Fig. 3.17
Rear exit
Side exit
*
*
= 190 mm ecoMAX
combination and system boilers
*
= 176 mm ecoMAX pro
*
= 125 mm ecoTEC
*
= 190 mm ecoMAX combination and system boilers
*
= 176 mm ecoMAX pro
*
= 125 mm ecoTEC
834449_05GB_022005.qxd 02.02.2005 17:12 Uhr Seite 22
Содержание ecoMAX 618/2 E
Страница 2: ...834449_05GB_022005 qxd 02 02 2005 17 12 Uhr Seite 2...
Страница 58: ...Notes 834449_05GB_022005 qxd 02 02 2005 17 13 Uhr Seite 58...
Страница 59: ...Notes 834449_05GB_022005 qxd 02 02 2005 17 13 Uhr Seite 59...
Страница 60: ...834449_05 GB 02 2005 834449_05GB_022005 qxd 02 02 2005 17 13 Uhr Seite 60...