PLANNING THE AIR/FLUE DUCT LAYOUT
Maximum flue lengths for use with ecoTEC
PA
R
T 2 CONCENTRIC 80/125
Accessories
Accy. No.
Vertical
flue systems
303 200 Max. permitted
concentric
flue length
Horizontal
flue systems
303 209 Max. permitted
concentric
flue length
14.0 m
13.0 m
incl.
1 elbow 87°
27.0 m
27.0 m
25.0 m
incl.
1 elbow 87°
25.0 m
incl.
1 elbow 87°
14.0 m
13.0 m
incl.
1 elbow 87°
plus 612
plus 615
plus 618
plus 624
ecoTEC
Maximum length of flue is reduced by 2.5 m for each additional 90° elbow.
Maximum length of flue is reduced by 1.0 m for each additional 45° elbow.
Maximum length of flue is reduced by 2.5 m for each additional 90° elbow
Maximum length of flue is reduced by 1.0 m for each additional 45° elbow
Accessories
Accy. No.
Vertical
flue systems
303 200 Max. permitted
concentric
flue length
Horizontal
flue systems
303 209 Max. permitted
concentric
flue length
27.0 m
25.0 m
incl.
1 elbow 87°
27.0 m
27.0 m
25.0 m
incl.
1 elbow 87°
25.0 m
incl.
1 elbow 87°
27.0 m
25.0 m
incl.
1 elbow 87°
plus 630
plus 824
plus 831
pro 28
ecoTEC
Maximum length of flue is reduced by 2.5 m for each additional 87° elbow.
Maximum length of flue is reduced by 1.0 m for each additional 45° elbow.
Maximum length of flue is reduced by 2.5 m for each additional 90° elbow
Maximum length of flue is reduced by 1.0 m for each additional 45° elbow
834449_05GB_022005.qxd 02.02.2005 17:12 Uhr Seite 43
Содержание ecoMAX 618/2 E
Страница 2: ...834449_05GB_022005 qxd 02 02 2005 17 12 Uhr Seite 2...
Страница 58: ...Notes 834449_05GB_022005 qxd 02 02 2005 17 13 Uhr Seite 58...
Страница 59: ...Notes 834449_05GB_022005 qxd 02 02 2005 17 13 Uhr Seite 59...
Страница 60: ...834449_05 GB 02 2005 834449_05GB_022005 qxd 02 02 2005 17 13 Uhr Seite 60...