On-roof mounting: 

The tube collectors can be mounted at an angle of 
15° – 75°.
An installation angle of less than 15° is not permissible.

Flat roof installation:

The tube collectors can be installed on flat roof frames 
in the as-delivered condition with an angle of 30°, 45° 
or 60°.
An installation angle of less than 15° is not permissible.

3 Safety 

instructions

The following safety instructions, technical rules and ac-
cident prevention regulations must be observed when 
installing the flat collectors.

d

 Danger!

Risk of death from falls and falling objects!
Observe the national regulations for working at 
heights.

H

 Danger!

Danger of burning and scalding!
In case of solar irradiation inside the units, col-
lectors can reach 300 °C. Remove the sun pro-
tection film installed at the factory only after 
the solar energy system has been started up.

H

 Danger!

Danger of burning and scalding!
In case of solar irradiation inside the units, col-
lectors can reach 300 °C. 
Do not perform maintenance work under direct 
sunlight.

a

 Caution!

Collector damage!
A qualified engineer is required to install tube 
collectors in accordance with this installation 
manual. 
The installation should thus be performed only 
if a qualified engineer is available.

3.1 Technical 

Guidance

The system must be installed in accordance with all rel-
evant and applicable national regulations, and must be 
installed to suit site conditions.
Observe all national regulations, including:
- Working at Heights Regulations 2005
- Health and Safety at Work Act 1974
- Electricity at Work Regulations 1989
- IEE Wiring Regulations BS 7671
- Lightning protection requirements
- Equipotential bonding of electrical installations.

3.2 Related 

documents

Designers and installers should refer to current informa-
tion and standards. A useful reference would be the en-
ergy saving trust document CE 131 (this is downloadable 
from their web site at www.est.org.uk/housingbuildings) 
which lists relevant standards and other documents that 
you might refer to. This includes but is not limited to the 
following; 
Solar Standards 
BS 7431, BS 6785: 1986, BS EN 12975 / 6 (Pt1-2), prEN 
12977 (1-2-3) BS EN ISO 9488
The installation of the solar system must be in accord-
ance with the relevant requirements of Health and Safe-
ty Document No. 635 (The Electricity at Work Regula-
tions 1989), BS7671 (IEE Wiring Regulations) and the 
Water Supply (Water Fitting) Regulations 1999, or The 
Water Bylaws 2000 (Scotland). It should also
be in accordance with the relevant requirements of the 
Local Authority, Building Regulations, The Building Reg-
ulations (Scotland), The Building Regulations
(Northern Ireland) and the relevant recommendations of 
the following British Standards:
-  BS EN 806: Specification for installations inside build-

ings conveying water for human consumption

–  BS 6700: Services supplying water for domestic use 

within buildings and their curtilages.

-  BS. 5449 Forced circulation hot water central heating 

systems for domestic premises. 
Note: only up to 45 kW.

-  BS. 6880 Low temperature hot water heating systems 

of output greater than 45 kW. 
Part 1 Fundamental and design considerations.
Part 2 Selection of equipment.
Part 3 Installation, commissioning and maintenance.

–  BS 6114: Expansion vessels using an internal dia-

phragm for unvented hot water supply systems

-  BS. 4814 Specification for: Expansion vessels using an 

internal diaphragm, for sealed hot water heating sys-
tems.

Unvented hot water systems must comply with building 
regulation G section 3.

3.3 

Regulations for the prevention of accidents

When carrying out works such as solar installation work 
it is necessary to do so in a safe and workman like man-
ner, taking due care of any aspects of the works that 
could result in injuries to person in or about the building 
as well as workers, passers by and the general public at 
large. To that end these works must conform, but
not be limited to, the current regulations in force such 
as the following
-  Health and Safety at Work act 1974
-  Work at Height Regulations 2005.
-  Electricity at Work Regulations 1989
-  All necessary Building Regulations.
Work should be preceded by a risk assessment covering 
all aspects of health and safety risks, or training re-
quirements that can reasonably be foreseen to be

Installation manual auroTHERM 0020077994_00

4

2 Intended use
3 Safety instructions

Содержание auroTHERM VTK 570/2

Страница 1: ...For the expert technician Installation manual auroTHERM On roof flat roof installation VTK 570 2 VTK 1140 2 GB...

Страница 2: ...llector arrangement 1 row 8 4 3 1 2 Collector arrangement 2 row 10 4 3 1 3 Collector arrangement 3 row 11 4 3 2 Flat roof mounting 13 4 4 Interconnection scheme 14 4 5 Preparing the hydraulic connecti...

Страница 3: ...sed safety rules and regulations Nevertheless improper use may cause danger to life and limb of the user or third parties and could impair the operation of the unit and other objects The unit is not i...

Страница 4: ...ards BS 7431 BS 6785 1986 BS EN 12975 6 Pt1 2 prEN 12977 1 2 3 BS EN ISO 9488 The installation of the solar system must be in accord ance with the relevant requirements of Health and Safe ty Document...

Страница 5: ...n a Caution Damage due to frost Never fill or flush the collector with water Only fill and flush the collector with Vaillant ready mixed solar fluid Check the solar fluid regularly with an anti freeze...

Страница 6: ...t VTK expansion module Rail joining pieces Double nipple 15 x 15 mm Insulation Armeflex HT 25 x 20 mm 45lg Cover clip 1 0020076779 7 Valve 2 way VTK for parallel interconnection 1 0020076784 8 Bracket...

Страница 7: ...0020076780 3 Open air installation VTK 1 0020076778 4 Gravel tray kit 2 3 0020059904 2 pcs 0020059905 3 pcs 5 Tube collector VTK 570 2 1 0010002227 6 Tube collector VTK1140 2 1 0010002228 7 Valve 2 wa...

Страница 8: ...ting kit VTK basic module Part No 0020076785 Required quantity 11 Connecting kit VTK expansion module Part No 0020076779 1 2 3 4 5 6 7 8 9 10 11 12 13 Bracket kit Type P pantile Part No 0020067273 12...

Страница 9: ...K 1140 2 1 2 3 4 5 6 Number of collectors VTK 570 2 1 1 1 1 1 1 Connecting kit VTK basic module Part No 0020076785 Required quantity 11 Connecting kit VTK expansion module Part No 0020076779 1 2 3 4 5...

Страница 10: ...273 a 12 22 32 42 52 62 72 82 92 102 112 122 132 142 Bracket kit Type S Part No 0020067275 Bracket kit Type S flat Part No 0020080145 Bracket kit Type P pantile Part No 0020067274 B 12 22 32 42 52 62...

Страница 11: ...0020067275 Bracket kit Type S flat Part No 0020080145 Bracket kit Type P pantile Part No 0020067274 B 12 22 32 42 52 62 72 Bracket kit Type S Part No 0020067276 Bracket kit Type S flat Part No 002008...

Страница 12: ...780 3 6 9 12 15 18 21 24 27 30 33 36 39 42 Number of collectors per row 1 2 3 4 5 6 7 Number of rows 3 VTK 1140 2 Connecting kit VTK basic module Part No 0020076785 Required quantity 31 Connecting kit...

Страница 13: ...6779 1 2 3 4 5 6 Mounting kit for open air installation on a flat roof Part No 0020076778 2 3 4 5 6 7 8 Gravel trays required 8 12 16 20 24 28 32 Gravel tray 2 pcs Part No 0020059904 1 2 1 2 1 Gravel...

Страница 14: ...Series connection VTK 1140 2 Connect a maximum of 7x VTK 1140 2 corresponding to an aperture area of 14 m2 in series Fig 4 8 Parallel connection here VTK 570 2 For aperture areas greater than 14 m2 yo...

Страница 15: ...alve must be fitted in the collector supply line hot side of each individual array These will be used for venting the in dividual arrays during commissio ning Only use the Vaillant stop valve Part No...

Страница 16: ...mounting With on roof mounting the tube collectors are fastened to horizontal mounting rails quickly and reliably with at tachment clips To ensure a good adaptation to the dif ferent roofings four dif...

Страница 17: ...er of collectors A B C D VTK 570 2 1 1663 1638 50 100 507 607 707 2 1414 3 2121 4 2828 5 3535 6 4242 7 4949 8 5656 9 6363 10 7070 11 7777 12 8484 13 9191 14 9898 VTK 1140 2 1 100 200 997 1197 1397 2 2...

Страница 18: ...s VTK 570 2 1 1663 1638 50 100 507 607 707 3322 5006 2 1414 3 2121 4 2828 5 3535 6 4242 7 4949 8 5656 9 6363 10 7070 11 7777 12 8484 13 9191 14 9898 VTK 1140 2 1 1663 1638 100 200 997 1197 1397 3322 5...

Страница 19: ...5 3 3 Loosen the upper bolt with the socket combination wrench 13 mm until the height of the bracket can be adjusted 4 Position the bracket at the same height of the pan tiles so that the upper part...

Страница 20: ...xing to the roof batten 1 Slide upward one or two pantiles above the roof bat ten For distances please see Tab 5 1 and 5 2 2 Loosen the upper bolt with the socket combination wrench 13 mm until the he...

Страница 21: ...competent roofing contractor designer Before installation on the roof batten check the load capacity of the roof batten If necessary replace the roof batten or provide additional timber bearers Also...

Страница 22: ...osition For distances please see Tab 5 1 and 5 2 2 Tighten the stair bolt to the rafters through the pan tile 3 Screw the lower nut against the roof covering and tighten it until the seal sufficiently...

Страница 23: ...low as possible on the bracket Fig 5 10 Joining the mounting rails Insert the connecting elements into the mounting rails by the side until they lock into place Join the mounting rails and fix them wi...

Страница 24: ...g ele ments make sure the tension is cor rect by shaking the upper part of the clamping element If it can be moved retighten the nut 1 Fig 5 13 Peeling the film from the edges of the collector Lift th...

Страница 25: ...ple A from the VTK expansion module connecting kit Part No 0020076779 to the union nut B on the first collector Push the collectors together Fig 5 17 Tightening the compression fitting a Caution Dange...

Страница 26: ...ook of the clamping element 3 is above the edge of the colle ctor Fix the mounting rail 2 for the next row of collectors to the clamping element 2 1 3 Fig 5 20 Central mounting rail for 2 or 3 rows of...

Страница 27: ...bly To prevent damage when tightening the compression fitting always use a second spanner to provide a counter force Connect the collector supply and return to the system with the connection pipes To...

Страница 28: ...irst of all define the necessary load of the frames based on Tab 6 1 Load kg collector Height above ground Angle of attack 0 10 m 10 18 m 18 25 m 30 159 178 197 45 225 252 279 60 276 309 342 Table 6 1...

Страница 29: ...5 45 42 5 60 59 5 C D 30 A B F B F B F 1 5604 1072 2950 2 1432 3940 2 1757 4830 2 2460 2 1168 584 707 3 1875 4 2582 5 3289 6 3996 7 4703 8 5410 9 6117 10 6824 11 7531 12 8238 13 8945 14 9652 1 Instal...

Страница 30: ...C D 30 A B F B F B F 1 11704 1072 29502 1432 39402 1757 48302 2460 2 2548 1274 1397 3 3945 4 5342 5 6739 6 8136 7 9533 1 Angle of attack 30 45 or 60 2 Solar altitude of 20 winter sun 3 Dimension A ma...

Страница 31: ...A G B F B F B F VTK 570 2 VTK 1140 2 1 1 11704 1072 29502 1432 39402 1757 48302 2460 584 1397 1274 1 2 2548 1 3 3945 1 4 5342 1 5 6739 1 6 8136 1 Angle of attack 30 45 or 60 2 Solar altitude of 20 wi...

Страница 32: ...570 2 VTK 1140 2 1 Fig 6 2 Mounting the gravel trays If gravel trays are used Slide the gravel tray 1 on the base section Fasten the rear section to the base section with a retaining pin and locking...

Страница 33: ...connection With screwed connection on the roof Assembly frames based on the number of collectors to be installed h Note The weights and distances can be found in Table 6 1 Fix the frames on the roof...

Страница 34: ...tion the upper part 1 of the clamping element over the rail on the collector Tighten the clamping elements of the lower mounting rail with the socket combination wrench 13 mm AF a Caution After tighte...

Страница 35: ...he collectors Couple the double nipple A from the VTK expansion module connecting kit Part No 0020076779 to the union nut B on the first collector Push the collectors together Fig 6 14 Tightening the...

Страница 36: ...pening provi ded on the flow side of the collector hot side hNote It is possible to attach the collector sensor to the left or the right side of the collector array as the collectors have a correspond...

Страница 37: ...No 0020076779 7 Final operations Based on the following table make sure all work steps have been performed Step 1 For flat roof installation frames fixed with retaining pin and safety clip 2 For flat...

Страница 38: ...ated pipe work and controls must be installed by suitably competent persons in ac cordance with all current and relevant safety building control and planning regulations and in full compliance with th...

Страница 39: ...rption alpha 93 5 see also ITW test report Absorber emission epsilon 6 see also ITW test report Modular dimensions length x height x depth m 0 7 x 1 65 x 0 11 1 39 x 1 65 x 0 11 Gross area m2 1 16 2 3...

Страница 40: ...Installation manual auroTHERM 0020077994_00 40 VTK 570 2 1652 111 702 Fig 10 1 Dimensional drawing VTK 570 2 10 Technical data...

Страница 41: ...2 Fig 10 2 Dimensional drawing VTK 1140 2 0 0 10 20 30 40 50 60 70 80 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 T Fig 10 3 Efficiency of the VTK 570 2 and the 1140 2 at an ir radiance Eg of 300 W...

Страница 42: ...Fig 10 4 Efficiency of the VTK 570 2 and the 1140 2 at an ir radiance Eg of 800 W m2 Key K Efficiency T TCollector TAmbient air K 160 140 120 100 90 60 40 20 0 Q l h p mbar 0 50 100 150 200 250 300 3...

Страница 43: ......

Страница 44: ...0020077994_00 GB 022009 Modifications reserved...

Отзывы: