Installation manual auroTHERM 0020077994_00
14
4.4 Interconnection
scheme
h
Note
Observe the planning information when dimen-
sioning the array volume flow.
Furthermore, observe the following rules:
max. 14
Fig. 4.6 Series connection VTK 570/2
• Connect a maximum of
14x VTK 570/2
(corresponding to an aperture area of 14
m
2
) in series.
max. 7
Fig. 4.7 Series connection VTK 1140/2
• Connect a maximum of
7x VTK 1140/2
(corresponding to an aperture area of 14
m
2
) in series.
Fig. 4.8 Parallel connection (here VTK 570/2)
• For aperture areas greater than 14 m
2
, you
must configure several collector arrays in
parallel and connect them hydraulically in
parallel.
• Always connect as many collectors as pos-
sible in series.
h
Note
You should only connect the collec-
tor arrays in parallel if the aperture
area is greater than 7 m
2
(correspon-
ding to 7x VTK 570/2 or 3x 1140/2
+ 1x VTK 570/2).