background image

 

 

 

  

US Water Systems, Inc. 

1209 Country Club Road 

Indianapolis, IN 46234 

1-800-608-8792 

[email protected] 

www.uswatersystems.com 

 

REVISION 1.5, 10-31-14 

Owners Manual 

Models: 

089-FSF-XXX-OG 

US Water Systems 

Corporate Office 

1209 Country Club Road 
Indianapolis, IN 46234 

[email protected] 
www.uswatersystems.com 
1-800-608-8792 

Visit us online at  

www.uswatersystems.com

 

REVISION # 

1.7 

REVISION DATE 

March 22, 2017 

US Water Fusion Oxi-Gen Professional 

Grade Iron & Sulfur Removal System 

Содержание FSF-200-OG

Страница 1: ...10 31 14 Owners Manual Models 089 FSF XXX OG US Water Systems Corporate Office 1209 Country Club Road Indianapolis IN 46234 info uswatersystems com www uswatersystems com 1 800 608 8792 Visit us onli...

Страница 2: ...y Guide Be sure to check the entire system for any shipping damage or parts loss Also note damage to the shipping cartons Contact US Water Systems at 1 800 608 8792 to report any shipping damage withi...

Страница 3: ...terial after installation Small parts remaining after the installation could be a choke hazard The Fusion Oxi Gen system provides iron and sulfur removal throughout the home The Fusion Oxi Gen system...

Страница 4: ...ual Carbon may be multiple boxes Gravel Separate Box Distributor Tube Upper Basket Control Valve Parts Box Solution Tank 8 2 5 Gallons of Peroxide 4 Boxes Stenner Proportional Injection System Panel I...

Страница 5: ...its Fusion Oxi Gen System which utilizes Hydrogen Peroxide or H2O2 Hydrogen peroxide or H2O2 is a powerful yet versatile oxidant that is both safe and effective Considering the H2O2 advantages it s ea...

Страница 6: ...n This reaction is immediate When these contaminants are oxidized with hydrogen peroxide H2O2 the extra oxygen molecule oxidizes the contaminants and the by product is H2O water This is much safer tha...

Страница 7: ...ne The Catalytic Carbon is equipped with a bypass valve CAUTION Water pressure is not to exceed 80 psi water temperature is not to exceed 110 F 43 C and the unit cannot be subjected to freezing condit...

Страница 8: ...e Place the upper basket over the distributor tube and push the valve on the tank Thread the valve on the tank by turning it clockwise Be sure not to cross thread the valve on the tank Tighten the val...

Страница 9: ...mounting bar A level can be used to make sure the bar is installed properly This bar should be secured to the wall studs or wood backing plate that is secured to the wall studs Strainer Filter Sump 30...

Страница 10: ...om the sediment filter to the left side of the injection panel Use the 3 4 Union Adaptors to connect to the panel These adaptors are designed for 3 4 PVC If 1 plumbing is used the 1 x 3 4 Bell Reducer...

Страница 11: ...o not over tighten these unions 5 Now install the strainer filter and the strainer sump If the feed water is high in turbidity use the 100 mesh strainer filter All other applications should use the 30...

Страница 12: ...F 500 OG 1 There is a ball valve on the bottom of the strainer filter sump This ball valve should be closed during operation This ball valve and be used to flush the strainer filter sump period ically...

Страница 13: ...nectors into the bypass valve once they are tight in the plumbing fitting The red clips can then be re installed to se cure the connectors in the bypass valve The inlet and outlet can be identified on...

Страница 14: ...to check the stamped ar rows on the valve and bypass for inlet outlet orientation All piping should be secured to prevent stress on the bypass valve and connectors 7 Install the drain line on the con...

Страница 15: ...sh the 1 4 tubing in the hole in the tank 2 Pull the 1 4 tubing from inside the tank up through the fill hole Then push on the weighted strainer on the 1 4 Tubing Injection Panel Chemical Solution Tan...

Страница 16: ...ch the other end of the 1 4 tubing to the pump on the injection panel Put the nut over the tubing and then the sleeve Push the tubing in the pump fitting and tighten the nut hand tight The connection...

Страница 17: ...mp to the on position and allow the chemical pump to prime with peroxide Typically the peroxide can be seen traveling through the tubing Once the pump is primed unplug the pump from the extension cord...

Страница 18: ...ENERATION Press and release the MANUAL REGEN Button to set a delayed regeneration that will occur at the regeneration time The main dis play page will show DELAYED REGEN ON To cancel press and release...

Страница 19: ...he system is not regenerating during usage hours If there is other backwashing regenerating equipment be sure to offset the regeneration backwash times of each of those units so each unit can backwash...

Страница 20: ...slowly and allow water to enter the unit Allow all air to escape from the unit before turning the water on fully then allow water to run to drain for the entire backwash cycle or until all media fines...

Страница 21: ...nd dissipate immediately This should be the optimal H2O2 injection setting The bubbles should be in the center of the glass and rise to the top immediately Bubbles on the outside of the glass are not...

Страница 22: ...eing overfed with H2O2 This occurs because after installation the water will become cleaner after the plumbing system has been flushed and the initial dosage of H2O2 may need to be adjusted to compens...

Страница 23: ...scolored 6 12 Months Injection Pump Tube Inspect pump tube and replace as need ed 1 5 Years Injection Pump Duck Bill Check Valve Replace injection check valve as need ed 1 5 Years H2O2 Solution Tank P...

Страница 24: ...es Sediment Filter Housings or Chemical Solution Tanks damaged due to environmental issues or improper installation are not covered GENERAL PROVISIONS This warranty does not apply to any commercial or...

Отзывы: