LBT8633
4.14.23 IDP message structure
The control panel sends a message for every single event, in case of multiple events, it sends them all in one single call.
For example, in the event of total arming, the control panel sends, in succession during the same call, the arming
messages of each zone (in fact there is no total arming or disarming event).
This structure of the string is valid for all events.
A A A A 1 8 Q E E E G G C C C S
Rem.CTRL Code
FIXED
Qualif
EVENT
GROUP
Code or Input ID
Cks
Where:
AAAA
=
Rem.CTRL Code
are the last 4 digits of the Rem.CTRL.Code
Q =
QUALIFICATION
=
1
indicates the start of an event or disarming
=
3
indicates the end of an event or arming
EEE =
EVENT
=
100
emergency alarm from the input
=
101
emergency alarm from the function key on the keypad
=
110
fire alarm from the input
=
111
fire alarm from the function key on the keypad
=
120
audible panic alarm from the input
=
121
hold-up alarm from the input or user code + 1
=
122
silent panic alarm from the input or function key on the keypad
=
130
burglar alarms from the input
=
134
burglar alarms from the input from the way (entry / way / output)
=
137
tamper
alarms
=
138
pre-alarms from the input
=
150
technological event input
=
300
failure alarm from the failure input
=
301
lack of power alarms
=
302
low battery alarms
=
307
power supply failure alarms
=
354
PSTN or GSM telephone failure alarms
=
401
arming/disarming by user code or key
=
403
arming/disarming by Timing programmer (P.O.)
=
407
arming/disarming by remote user code with DTMF code or with FastPro
=
409
arming/disarming with key input
=
458
maintenance (installer working on site)
=
461
wrong
code
alarms
=
570
input
exclusion
=
601
manual test call
=
602
periodic communication test
GG =
GROUP
=
00
the event is related to the whole system
=
01 ÷ 08 the event is related to zone 1 ÷ 8
=
07
with “excluded input” event indicates manual exclusion
=
09
with “excluded input” event indicates autoexclusion
CCC
=
IDENTIFICATION CODE depending on the event
for arming events
=
000
event generated by Timing programmer (P.O.) or FastPro
to identify an user or a key
=
001
event generated by the master user code
=
002 ÷ 031 event generated by the 2 ÷ 31 user code
=
101 ÷ 132 event generated by the 1 ÷ 32 key
to indicate an input
=
0
du
control panel input, logical address (d=tens u=unit)
=
1
du
input of a keypad, logical address (d=tens u=unit)
=
3
du
input of a reader, logical address (d=tens u=unit)
=
4
du
input of an expansion, logical address (d=tens u=unit)
to indicate the keypad that has generated an event with function key
=
101 ÷ 108 event generated by the 1 ÷ 8 keypad
to indicate the device that has generated the tamper alarm for tamper
=
000
event generated by tamper or SAB input of the control panel
=
101 ÷ 108 event generated by the 1 ÷ 8 tamper keypad
=
400 ÷ 400 event generated by the tamper of an expansion
to indicate the device that has generated the failure alarm for communication loss
=
101 ÷ 108 event generated by the lack of communication of the 1 ÷ 8 keypad
= 401 ÷ 408 event generated by the lack of communication of the 1 ÷ 8 expansion