background image

UNITED FIRE SYSTEMS 

STANDPIPE-PAC

™ MODEL SSS-101 

DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL 

REVISION 2.00 

P/N 10-540101-001 

 

 

UNITED  Fire  Systems 

STANDPIPE-

PAC™

  standpipe  supervisory  systems  are  to  be  installed,  operated,  and 

maintained by qualified, trained personnel in accordance with: 

 

This Installation, Operation, and Maintenance Manual P/N 10-540101-001 Revision 2.00. 

 

National  Fire  Protection  Association  No.  14

,  “Standard  for  the  Installation  of  Standpipe  and  Hose 

Systems.” 

 

National Fire  Protection  Association No. 25, 

“Standard for the Inspection, Testing, and Maintenance 

of Water-Based Fire Protection Systems

.” 

 

National Fire Protection Association No. 70, “National Electrical Code®”. 

Any questions on the information in this manual should be addressed to: 

UNITED Fire Systems, Division of United Fire Protection Corporation 

1 Mark Road, Kenilworth, NJ USA 07033 

908-688-0300  

www.unitedfiresystems.net

  

 

LIMITED WARRANTY 

STANDPIPE-

PAC™ 

What Does This Warranty Cover? 

This warranty covers all manufacturing defects in material and workmanship in your new 

STANDPIPE-

PAC™.

  

How Long Does The Coverage Last? 

This warranty lasts for ninety (90) days from the date of shipment to the original purchaser. 

What Will UNITED Fire Systems Do? 

UNITED  Fire  Systems  will  repair,  replace,  or  refund  the  purchase  price  of,  at  its  option,  any  defective 

STANDPIPE-

PAC™

 at no charge.  

What Does This Warranty Not Cover? 

STANDPIPE-PAC

™s that have NOT been commissioned by UNITED Fire Systems or a trained distributor are 

not  covered  under  this  warranty.    If  you  modify,  change,  or  alter  your 

STANDPIPE-

PAC™

  without  instructions 

from  UNITED  Fire  Systems,  the 

STANDPIPE-

PAC™

  is  not  covered.        If  you  break  tamper  seals  applied  by 

UNITED Fire Systems, the sealed parts are not covered.  Any problem that is caused by abuse, misuse, or an 
act  of  God  (such  as  a  flood)  is  not  covered.    Also,  consequential  and  incidental  damages  are  not  recoverable 
under this warranty. Some states do not allow the exclusion or limitation of incidental or consequential damages, 
so the above limitation or exclusion may not apply to you.  

How Do You Obtain Service? 

In order to be eligible for service under this warranty, your 

STANDPIPE-

PAC™

 must have been commissioned 

by  UNITED  Fire  Systems  or  a  trained  distributor

.  If  something  goes  wrong  with  your 

STANDPIPE-

PAC™,

 

contact:  

UNITED Fire Systems 

Division of UNITED Fire Protection Corporation 

1 Mark Road 

Kenilworth, NJ  07033 USA 

Phone: 908-688-0300 

Fax:  908-481-1131 

= OR = 

Your 

Trained 

Distributor 

 
UNITED Fire Systems or your trained distributor will contact you within 24 hours to arrange for evaluation of your 

STANDPIPE-PAC

™.

 

Is This Warranty Transferable? 

If the 

STANDPIPE-

PAC™

 is moved from one to another installation during the time period of warranty coverage, 

the 

STANDPIPE-

PAC™

  must  be  re-commissioned  by  UNITED  Fire  Systems  or  your  trained  distributor  to  be 

eligible for continuing coverage.  You must pay a quoted charge for this re-commissioning. 

Is This The Entire Warranty? 

This  limited  warranty  is  the  entire  warranty  given  by  UNITED  Fire  Systems  to  the  purchaser  of  a  new 

STANDPIPE-

PAC™.

  There are no other warranties expressed or implied, beyond those required by law. 

How Do State and Federal Laws Apply? 

This warranty  gives  you specific legal rights per Federal  law.   You may also have other rights  which vary from 
state to state.  

Содержание STANDPIPE-PAC SSS-101

Страница 1: ..._____________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth NJ USA 07033...

Страница 2: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Страница 3: ...mining Proper STANDPIPE PAC To Use 5 2 4 Example 1 6 2 5 Example 2 7 2 6 Options 8 2 6 1 Additional Audible Signals 8 2 6 2 Off Site Signaling Via Dialer 8 3 INSTALLATION 3 1 Unpacking 9 3 2 Location...

Страница 4: ...32 4 4 5 To Refill Standpipe With Air Pressure After Fire Department Use 33 4 4 6 To Test Standpipe with Water Pressure 34 5 MAINTENANCE 36 5 1 Weekly 37 5 2 Monthly 37 5 3 Quarterly 38 APPENDICES App...

Страница 5: ...formation is provided for the safety of installers operators and users of the UNITED Fire Systems STANDPIPE PAC equipment Carefully read understand and follow instructions identified by these symbols...

Страница 6: ...ate at the time of publication but the data is published and presented without any guarantee or warranty whatsoever UNITED Fire Systems disclaims any liability for any use that may be made of the data...

Страница 7: ...STANDPIPE PAC without instructions from UNITED Fire Systems the STANDPIPE PAC is not covered If you break tamper seals applied by UNITED Fire Systems the sealed parts are not covered Any problem that...

Страница 8: ...air dryer dries the compressed air before entry into the standpipe as required by Boston FD TCM3 51725 3 Low limit pressure sensing switch This switch senses when the pressure in the standpipe drops b...

Страница 9: ...side the location of the STANDPIPE PAC and wire the device in accordance with the instructions in this manual 17 An auxiliary condensate drain device This device permits manual draining of water in th...

Страница 10: ...2 00 P N 10 540101 001 Page 3 INSTRUCTION NAMEPLATE 15 MANUAL AIR RELEASE BLEED VALVE CAP AND CHAIN Figure 2 Manual Air Release Bleed Valve Figure 4 Auxiliary Condensate Drain Device 17 AUXILIARY COND...

Страница 11: ...determined by multiplying the length of each pipe by size by the internal volume per foot in gallons Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 1 1 2 X 0 106 2 X 0 174 2 1 2 X 0 2...

Страница 12: ...the desired fill time at the bottom of the graph 2 3 2 Find the standpipe internal volume at the left of the graph 2 3 3 Determine the intersection of the lines from these two values 2 3 4 Choose the...

Страница 13: ...101 001 Page 6 2 4 Example 1 Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 6 750 X 1 500 1125 TOTAL 1125 gallons Required work can be performed in 1 2 hour 30 minutes so a fill time o...

Страница 14: ...e 2 Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 2 80 X 0 174 14 6 100 X 1 500 150 8 550 X 2 600 1430 TOTAL 1594 gallons Fill time of 1 hour 60 minutes required Figure 7 Design Examp...

Страница 15: ...his manual for further information See Paragraph 3 3 5 5 for installation instructions 2 6 2 Off Site Signaling Via Dialer The STANDPIPE PAC control unit is equipped with a built in dialer for off sit...

Страница 16: ...3 2 1 Temperature Ensure that the STANDPIPE PAC unit is installed in a location that will not drop below 32 F 0 C at any time This may be accomplished by Choosing a location that will be supplied wit...

Страница 17: ...t least 3 feet of clearance for personnel to access equipment for maintenance 3 3 Installation 3 3 1 Mounting See Figure 8 Mount the STANDPIPE PAC in the chosen mounting location It is strongly recomm...

Страница 18: ...regular basis permitting any water accumulation or pooled water from testing to drain Dry standpipes installed with supervisory systems shall be installed per Figure 9 above The diagram indicates sev...

Страница 19: ...and discard plastic plug from device inlet Valve 1 3 See Figure 10 Attach a inch close pipe nipple and the bull of a inch pipe tee to device inlet Valve 1 4 Install a convenient length of inch thread...

Страница 20: ...1 60 3 4 10 6 0 7 11 3 3 3 5 3 Power Wiring See Table 3 Choose minimum conductor sizes and overcurrent protective device based on total current shown in table Connect power in junction box provided fo...

Страница 21: ...NDPIPE PAC MODEL SSS 101 DESIGN INSTALLATION OPERATION AND MAINTENANCE MANUAL REVISION 2 00 P N 10 540101 001 Page 14 3 3 5 4 Battery Wiring See Figure 11 DO NOT connect battery until commissioning Fi...

Страница 22: ...5 5 4 Optional Signaling Devices If additional audible devices are desired connect these devices to the notification appliance circuit serving the signal horn on the STANDPIPE PAC unit See Appendix D...

Страница 23: ...9 optional signal horns Maximum Current Draw FOR ALL external Signal Horns INCLUDING required external audible visual device NOT including factory installed signal horn 1 0 A Maximum Length Of Notific...

Страница 24: ...rn assembly on STANDPIPE PAC En End of Line Resistor 3 See Figure 13 2 Visually inspect Signal Horn base plate connections Locate positive and negative terminals on base plate NOTE RED wire connects t...

Страница 25: ...all raceway from factory installed Signal Horn back box to additional Signal Horn NOTE See Table 4 for distance limitations 8 See Figure 13 6 Run 14 AWG Solid wires from additional Signal Horn through...

Страница 26: ...Connect wires at additional Signal Horns IMPORTANT Do not branch Signal Horn circuit Run circuit from the first Signal Horn to the second Signal Horn then the second Signal Horn to the third and so on...

Страница 27: ...ent capacity of the circuit when adding additional horns to the STANDPIPE PAC Each additional horn adjusted to FULL VOLUME draws 0 047 amps As noted on page 1 the current for all external devices incl...

Страница 28: ...and 18 PSIG should be adequate for supervising the standpipe and providing prompt signaling if a valve is opened or a portion of the standpipe is removed Setting the HIGH pressure signal at 23 PSIG 2...

Страница 29: ...ON 10 Press RESET button on control unit AC POWER indicator should be ON 11 ALARM indicator should be ON Signal horn should be sounding 12 Press SILENCE switch to acknowledge alarm Press SILENCE switc...

Страница 30: ...lear and ALARM indicator should be OFF 12 When pressure gauge needle reaches approximately 18 PSIG compressor should automatically shut off HIGH LIMIT PRESSURE SENSING SWITCH TEST 13 Verify that compr...

Страница 31: ...115 VAC not properly connected in junction box Properly connect power in junction box 3 3 5 3 STANDPIPE PAC does not build sufficient pressure in standpipe less than 7 PSIG One or more outlet valves o...

Страница 32: ...nstalled in area where temperature cannot go below 32 degrees F Color of beads in air dryer has changed Air dryer beads have absorbed water to their capacity Compare color of beads to decal on side of...

Страница 33: ...unit outlet lockable shutoff valve OPEN Has the battery been connected to the control unit Has 115 VAC power been turned ON Has the control unit RESET button been operated and is the control unit AC P...

Страница 34: ...device been operated and is the pressure gauge needle moving UP When the pressure gauge needle reaches approximately 23 PSIG does the control unit ALARM indicator come ON and do the signals operate Ha...

Страница 35: ...toff valve Is the control unit door locked Have the control unit keys lockable shutoff valve key s and UFS Manual P N 10 540101 001 been given to the responsible individual at the job site If the cont...

Страница 36: ...s a yellow LED visible with unit door closed or open indicating trouble with the backup battery 4 1 3 5 Visual Indicator SYSTEM TRBL This is a yellow LED visible with unit door closed or open indicati...

Страница 37: ...ON INDICATOR or CONTROL ITEM STATUS Visual Indicator Pressure Gauge Indicating between 13 and 18 PSIG Visual Indicator AC POWER ON Visual Indicator ACTIVE Off Visual Indicator COMM FAIL Off Visual Ind...

Страница 38: ...ignal Operation High Pressure In Standpipe If pressure increases in standpipe above 25 PSIG the following will be indicated HIGH PRESSURE IN STANDPIPE INDICATOR or CONTROL ITEM STATUS Visual Indicator...

Страница 39: ...sor Disconnect Switch ON Control Test Service Device Not Operated 4 4 2 To Silence Piezo Sounder Press ACKNOWLEDGE SILENCE HOLD 2 SEC pushbutton once 4 4 3 To Silence Signal Horns Press ACKNOWLEDGE SI...

Страница 40: ...ating less than 7 PSIG Visual Indicator AC POWER ON Visual Indicator ACTIVE ON Visual Indicator COMM FAIL Off Visual Indicator BATT FAULT Off Visual Indicator SYSTEM TRBL Off Visual Indicator SUPERVIS...

Страница 41: ...points or traps without drains CLOSE Lockable Shutoff Valve BEFORE testing standpipe with water pressure Perform pressure test Use main drain and all drainage valves at low points to drain all water f...

Страница 42: ...ry Condensate Drain Device to drain all water from piping in the vicinity of the STANDPIPE PAC It may take time for water to migrate from upper floors Allow sufficient time with drains open for all wa...

Страница 43: ...PAC pressure gauge are APPROXIMATE Variation from nominal values can be expected IMPORTANT The STANDPIPE PAC unit including control unit has been pre wired and programmed at the factory for proper ope...

Страница 44: ...in intact and connected to valve Valve OPEN Cap Disconnected or Missing If valve is OPEN CLOSE valve tightly If cap is disconnected re connect If cap is missing contact service provider for replacemen...

Страница 45: ...For this reason it is recommended that the dryer desiccant be replaced quarterly NOTE Refer to Figure 15 1 Have Qty 1 UFS P N 21 100000 100 Replacement Desiccant available 2 Notify local personnel tha...

Страница 46: ...se Qty 1 UFS P N 21 100000 100 13 Carefully align and insert desiccant bowl back into assembly until it is flush against air dryer cap 14 Depress tab marked PUSH and turn connecting ring until connect...

Страница 47: ...compressor disconnect switch to OFF 3 Use 5 32 hex key to remove 2 hex screws holding black filter housing in place 4 Remove filter housing 5 Remove and discard existing foam filter element 6 Replace...

Страница 48: ...ew filter 7 Monthly Has the Auxiliary Condensate Drain Device been properly used to remove water from the piping in the vicinity of the STANDPIPE PAC 8 Quarterly Has the HIGH PRESSURE signal been chec...

Страница 49: ...LL CORRECTIONS REPAIRS MADE LIST ALL CORRECTIONS REPAIRS NEEDED NOTES PRINT NAME SIGNATURE DATE INSPECTOR CUSTOMER INSPECTION MAINTENANCE CHECKLIST STANDPIPE PAC SUPERVISORY SYSTEM UFS 236 REVISION 2...

Страница 50: ...N 1 Remove Cover Cover is held on by two tamper resistant screws Removal key is en closed with pressure switch 2 Mounting the Switch The device is designed to be mounted in the upright or horizontal p...

Страница 51: ...D770 08 00 2 I56 0551 009R System Sensor 2014 System Sensor warrants its enclosed pressure switch to be free from defects in materials and workmanship under normal use and service for a period of thr...

Страница 52: ...to be mounted in the upright position side mounting is also acceptable Locate it where vibration shock and mechanical loading are minimal Refer to piping diagram above Fig 2 and 3 a Mount the device...

Страница 53: ...W TRIP POINT SW1 SW2 MODELS EPS40 2 EPS120 2 SWITCHES AT HIGH TRIP POINT SW1 SW2 B COM A B COM A B COM A A COM B A COM B A COM B DUAL SWITCH MODEL EPS40 2 AND EPS120 2 1 Install pressure switch as sta...

Страница 54: ...tion Perform pre ventive maintenance and periodic testing as required by the applicable NFPA standards but not less than bimonthly Install a back up control for all critical applications where control...

Страница 55: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Страница 56: ...d the life of the coalescing element Specifications X06 X03 Plastic Bowl X03 Metal Bowl X04 X25 Metal Bowl Maximum Pressure 150 psig 10 3 bar 150 psig 10 3 bar 150 psig 10 3 bar 150 psig 10 3 bar 150...

Страница 57: ...ge meaning dry to dark green meaning wet 3 By installing two or more units in parallel higher dry airflows can be achieved Maintenance 1 The only servicing required for silica gel units is when the de...

Страница 58: ...95 623 1 8 Clamp Ring GRP 96 404 1 GRP 96 404 1 NNR Not normally replaced The moisture indicator contains a weep orifice to provide an air sample to the moisture indicating paper Air leakage from thi...

Страница 59: ...rated plastic bowl with a bowl or a new plastic bowl and bowl guard CAUTION Except as otherwise specified by the manufacturer this product is specifically designed for compressed air service and use w...

Страница 60: ...ould be settled directly with the freight company WARNING Do not operate this compressor if damaged during shipment handling or use Damage may result in bursting and cause injury or property damage Lo...

Страница 61: ...ed electrician wire the compressor to ensure that the supply line has the same characteristics voltage frequency and phasing as the motor Wiring must comply with all local and national codes CAUTION I...

Страница 62: ...RCE THEN RELEASE ALL PRESSURE FROM THE SYSTEM BEFORE ATTEMPTING TO INSTALL SERVICE RELOCATE OR PERFORM ANY SERVICE The following instructions are based on NORMAL operation If the compressor is in an e...

Страница 63: ...voltage to start motor Increase wire size if necessary to lower voltage drop 2 Consult factory adjust or replace 3 Be sure fuses and heaters are rated properly 4 Add receiver vessel or increase pipe...

Страница 64: ...NGLE PHASE WIRING INSTRUCTIONS OIL LESS COMPRESSOR NOTE MOST MOTORS ARE MULTIPLE VOLTAGE CHECK NAMEPLATE AND VERIFY CORRECT INTERNAL CONNECTIONS FOR VOLTAGE BEING SUPPLIED TO UNIT FEEDER WIRE SIZE MUS...

Страница 65: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Страница 66: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Страница 67: ..._____________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth NJ USA 07033...

Отзывы: