UNITED FIRE SYSTEMS
STANDPIPE-
PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540000-001
Page 40
5.3.2. Replacement of Compressor Filter.
The compressor filter keeps dust and other contaminants
out of the compressor pump. Quarterly replacement can lengthen the lifespan of the compressor.
1. Have replacement filter kit UFS P/N 00-100005-553 available.
2. Move compressor disconnect switch to OFF.
3.
Use 5/32” hex key to remove (2) hex screws holding black filter housing in place.
4. Remove filter housing.
5. Remove and discard existing foam filter element.
6. Replace with new foam filter element from replacement filter kit.
7. Replace black filter housing.
8.
Secure filter housing with (2) hex screws using 5/32” hex key to tighten. Do not over-tighten.
9. Move compressor disconnect switch to ON.
5.3.3
When quarterly maintenance is complete, sign and date the Quarterly Maintenance Tag. Enter date
when next quarterly maintenance is due.
Filter
Figure 16
– Compressor Filter
Содержание STANDPIPE-PAC SSS-101
Страница 2: ...THIS SURFACE DELIBERATELY LEFT BLANK...
Страница 55: ...THIS SURFACE DELIBERATELY LEFT BLANK...
Страница 65: ...THIS SURFACE DELIBERATELY LEFT BLANK...