UNITED FIRE SYSTEMS
STANDPIPE-
PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 32
4.4. Procedures
4.4.1. Normal Operation.
Under normal operation, no intervention is needed.
NORMAL OPERATION
INDICATOR or CONTROL
ITEM
STATUS
Visual Indicator
Pressure Gauge
Indicating between 13 and 18 PSIG
Visual Indicator
AC POWER
ON
Visual Indicator
ACTIVE
Off
Visual Indicator
COMM. FAIL
Off
Visual Indicator
BATT. FAULT
Off
Visual Indicator
SYSTEM TRBL
Off
Visual Indicator
SUPERVISORY
Off
Visual Indicator
GND FAULT
Off
Audible Indicator
Piezo Sounder
Off
Audible Indicator
Signal Horn
Off
Control
Lockable Shutoff Valve
Open
Control
Compressor Disconnect Switch
ON
Control
Test / Service Device
Not Operated
4.4.2. To Silence Piezo Sounder.
Press
“ACKNOWLEDGE SILENCE (HOLD 2 SEC.)” pushbutton once.
4.4.3. To Silence Signal Horns.
Press “ACKNOWLEDGE SILENCE (HOLD 2 SEC.)” pushbutton once,
followed by pressing and holding the pushbutton for 2 seconds.
4.4.4. For Fire Department Use of Fire Standpipe.
Open Manual Air Release Bleed Valve located in proximity to fire department siamese.
Allow air to bleed from fire standpipe for 3 minutes.
Close Manual Air Release Bleed Valve before pumping water into fire standpipe.
WARNING
The fire standpipe MUST only be placed into use by the fire department. DO NOT use the standpipe for
any other purpose. Failure to follow this warning may result in impairment of the standpipe in the event of
fire, and may result in death, personal injury, or serious property damage when firefighters cannot fight a
fire.