28
5
SETTING OF FUNCTIONS
28
SE
TT
IN
G
O
F F
U
N
C
TIO
N
S
Chapter
5
5-1.
Digital Zero
The indicated values is forcedly zeroed.
■
Digital zero / digital zero reset by means of keys
With respect to torque, digital zero can be executed. Digital zero reset can also be executed.
1.
Press the [DZ] button in the ordinary
display screen (COMP
・
GRAPH).
2.
Press the [YES] button to
perform the digital zero.
Press the [NO] button to
go back to the previous
screen without executing
digital zero.
Press
the
[RESET]
button to reset the digital
zero.
■
Digital zero by means of external I/O signal (D/Z input)
The digital zero may be performed by short circuiting the D/Z to the COM2 on the rear panel signal
I/O terminal block, digital zero functions to zero torque.
5
SETTING OF FUNCTIONS
YES
NO
D/Z
OFF
ON
Keep on for 1.0 msec. or more.
CAUTION
- When digital zero is performed, if the difference from the zero calibration point
exceeds the digital zero limit, the digital zero limit error (DZ Err) will result.
Also, only the digital zero limit is subtracted.
- When digital zero reset is performed, the condition previous to correction by digital
zero is restored.
- Digital zero is reseted in case of power failure.