of 69
6.1.2. Access level 2
Level 2 is for the personnel in charge for the fire protection; they shall be trained and authorized
to operate the fire control panel in the following conditions:
Duty Mode;
Fire condition;
Pre-Fire condition;
Fault condition;
Disabled component;
Information and adjustment.
To enter Access level 2, insert the key into the front panel in position
.
The following features of the fire control panel are accessible:
All features accessible at Level 1;
Switching off the outputs, activated upon fire condition (see sections 8, 9 and 10);
Exit of Fire condition (see section 8);
System functions of the fire control panel without entering SetUp Mode (see section 13).
6.1.3. Access level 3
Accessible for personnel trained and authorized to:
Reconfigure specific data
– of the protected site or of the fire control panel – saved in the
memory;
Maintain the fire control panel.
This level has two sublevels of access - 3A and 3B.
Level 3, sublevel 3A, is accessed through a password, entered at Access level 2. At this sublevel
the functions for reconfiguration of specific data for the protected site or the fire control panel are
accessible (see section 14).
Level 3, sublevel 3B is accessed when the fire control panel is opened. The following features are
accessible:
Replacing a burnt fuse;
Adding, removing and replacing a module;
Connecting fire alarm lines and executive devices.
6.1.4. Access level 4
Accessible for personnel trained and authorized by the Producer to repair the fire control panel
and to modify the software. Special means are required for access to this level.
6.2. Indications and buttons for control
Table 1 gives detail description of the indications for each status, Table 2 presents the basic
means for control. Appendix 1 shows the front panel of Fire control panel FS5200 with its visual
system for indication and control.
6.3. Function
Logical AND
of two lines
The function
Logical AND
gives the opportunity to set the following dependence between two
lines in one and the same module (Basic module or Additional module): the fire control panel will
enter Fire condition, phase Fire condition stage I, in each of the line (or in both of them) upon
activation of fire detectors in both lines.
The function does not affect manual call points. Upon activation of a manual call point (value of
the line current between Fire condition stage II and Short circuit) in a line, dependent on function
“Logical AND”, the fire control panel will enter Fire condition stage II in this line.
Upon activation of automatic fire detector (value of the line current between Fire condition stage I
and Fire condition stage II) in a line that is in Logical AND dependency by another line, the fire control
panel will enter
Pre-Fire condition in this line
– if there is no activated automatic fire detector or manual call
point in the other line;
Fire condition, phase Fire condition stage I in this line
– if there is an activated manual call
point in the other line, i.e. the fire control panel has already entered Fire condition, phase Fire
condition stage II in the other line;