UniPOS
Fire Control Panel FS5200
Instruction manual
Page
9
Revision 8/07.17
of 69
Configuration
Modules
Technical data
Basic
Additional
B
asi
c
M
od
ul
e
M
od
ul
e
5201
M
od
ul
e
5203
M
od
ul
e
5204
M
od
ul
e
5202
M
od
ul
e
5201
09
х
х
х
х
32 lines
2 relay outputs for fire condition
2 controllable outputs
1 relay output for fault condition
10
х
х
х
х
х
32 lines
10
relay
outputs
for
fire
condition
2 controllable outputs
1 relay output for fault condition
11
(Configuration
maximum)
х
х
х
х
х
32 lines
18
relay
outputs
for
fire
condition
2 controllable outputs
1 relay output for fault condition
All configurations include Power Supply Module.
Per customer request Interface Module and Modem Supply Module can be included in each
configuration.
4.3. Fire alarm lines
Maximum number of fire detectors in a line
- 32
Connecting line
- two-wire
Maximum resistance of a line
- 100
Output resistance of a line
- 164
4.4. Controllable outputs
Type
- potential
Electrical characteristics
-
(24±5)V/500mA
4.5. Common purpose relay outputs
Type
- potential free, switching
Electrical characteristics
- 3A/125VAC; 3A/30VDC
4.6. Relay output for fault conditions
Type
- potential free, switching
Electrical characteristics
- 3A/125VAC; 3A/30VDC
4.7. Performance
Control over fire alarm lines and controllable outputs for fault conditions (short circuit and
interruption) and automatic reset.
Detection of removed fire detector and automatic reset.
Ability to set the lines in dependency of the function “Logical AND”
Group addressing of manual call points and automatic fire detectors
Two phases of Fire condition, programmable time for Fire condition stage I, separately
for each line