UniPOS
Fire Control Panel FS5200
Instruction manual
Page 40
Revision 8/07.17
of 69
14.3. Menus
The menu contains the following subordinate menus and functions:
01 Line parameters
02 Fire control panel parameters
03 Adjustment of controllable outputs
04 Adjustment of relay outputs
05 Default parameters
06 Clear archive
07 Enter new password
14.3.1. Menu
Line parameters
Select the menu from the screen:
The menu contains up to 32 subordinate menus, one for each
line (for lines that do not exist in this particular configuration no
menu is displayed):
When the menu for a particular line is activated a screen with
the submenu for the parameters appears:
(The field
“NN ” contains the number of the selected line)
Each of the subordinated menus contains command screens or menus for the following line
parameters:
01 Number of confirmation checks for Fire condition:
The
field “Х” contains the number of checks - 1 to 3.
Repeated checks (two or three) are usually set for fire detectors that shall respond two or
three times before a decision for Fire condition is made. In this case the time for the second
and third check is included in the response time of the detector, not in the response time of the
control panel.
02 Check for removed fire detectors:
When the field
“ХХ” contains “No”, check for removed fire
detectors is
not performed; when it contains “Yes”, the
check is performed.
The check is feasible when the fire detectors are connected in compliance with the connection
diagram in Appendix 5a. The check is performed every 8 seconds by applying 5V voltage of
reverse polarity on the line.
03 Period for transition from Fire condition stage I to Fire
condition stage II:
“SSS” contains the period in seconds - 0 to 255s.
> Set Parameters <
> Line NN <
Time F1-F2 SSSs
> Set Parameters <
> Line NN <
Check RmvdFD ХХ_
> Set Parameters <
> Line NN <
Number Checks Х_
> Set Parameters <
> Line NN <
01 Number Checks
02 Check RmvdFD
> Set Parameters <
> Lines <
01 Line 01
02 Line 02
> Set Parameters <
01 Lines
02 Fire Panel