UniPOS
Fire Control Panel FS5200
Instruction manual
Page 19
Revision 8/07.17
of 69
The button does not affect nor is its action cancelled by the following events:
When Fire Condition is registered in a new line, or transition from Fire condition stage I to Fire
condition stage II the button shall activate the local sounder for Fire/Pre-Fire condition;
When Pre-Fire Condition is registered in a new line, the button will activate the local sounder
for Fire/Pre-Fire condition;
A new Fault condition shall activate the local sounder for Fault condition only.
The button is active at Access levels 1 and 2.
9.3.2. Button
(Menu)
Press the button to enter Information and Control Mode.
10. Fault condition
10.1. Description
The fire control panel enters Fault Condition when any of the events below has been registered:
Fatal System fault, including New configuration;
Battery Low
– backup batteries discharged due to interruption in mains supply;
Fault in the program of Linear processor 2;
Fault in the data of Linear processor 2;
Fault in the program of Linear processor 3;
Fault in the data of Linear processor 3;
Failure in the real time clock;
Failure in the external memory;
Wrong record in the external memory;
Fault in a line
– removed fire detector, short circuit or break;
Fault in a controllable output
– short circuit or break;
Fault in main supply;
Fault in backup batteries power supply;
Short circuit in grounded wire;
Fault in the positive supply to the lines;
Fault in the negative supply to the lines;
Fault in power supply to external devices
Where a
Fatal System fault
occurs (except for New configuration) the main processor is not able
to continue operation. In this case:
only the linear processors that service the fire alarm lines and the controllable outputs are in
operation;
phase Fire condition stage I is ignored and if an automatic fire detector is activated, the control
panel enters Fire condition, phase Fire condition stage II;
in Fire condition will be activated Relay output 1 and Controllable output 1 (for lines 1
– 16) or
Controllable output 2 (for lines 17
– 32); the rest of the relay outputs for fire condition do not
function;
if the defected component is the LCD display, the information on it is not correct;
from the LED indication only
(Fault condition),
(System fault),
(Fire
condition stage II) and
(Power supply) are functioning;
the buttons do not work.
You can exit the fault condition if you disconnect the control panel from the mains supply and
send it for repairs.
New configuration
is a fatal system fault
– the fire control panel does not service lines, outputs or
other peripherals. To exit the condition you shall enter SetUp Mode. Such fault condition occurs
usually after modification of the physical configuration of the fire control panel
– addition, removal or
replacement of additional module.
Battery Low
is a fatal non-system fault
– the control panel does not service fire alarm lines or
outputs. The unit enters a specific condition:
Discontinuous sound signal is released - 1s sound, 3s pause, for at least an hour;