UniPOS
Fire Control Panel FS5200
Instruction manual
Page 38
Revision 8/07.17
of 69
Fault Code 2 Reset
– fire control panel exits Fault condition: Fault in the
program of Linear processor 2;
Fault Code 3
– fire control panel enters Fault condition: Fault in the program of Linear
processor 3;
Fault Code 3 Reset
– fire control panel exits Fault condition: Fault in the
program of Linear processor 3;
Fault Data 2
– fire control panel enters Fault condition: Fault in data of Linear
processor 2;
Fault Data 2 Reset
– fire control panel exits Fault condition: Fault in data of
Linear processor 2;
Fault Data 3
– fire control panel enters Fault condition: Fault in data of Linear
processor 3;
Fault Data 3 Reset
– fire control panel exits Fault condition: Fault in data of
Linear processor 3;
Fault Timer
– fire control panel enters Fault condition: Real time clock failed;
Fault Timer Reset
– fire control panel exits Fault condition: Real time clock
failed
Fault DataEEPROM
– fire control panel enters System fault: Wrong record in internal
EEPROM of Processor 1;
Fault Code 1
– fire control panel enters System fault: Fault in the program of
Processor 1;
Fault Data 1
– fire control panel enters System fault : Fault in the data of Processor 1;
Fault Display
– fire control panel enters System fault: Display failed;
New configuration
– fire control panel enters System fault : New configuration;
Battery Low
– fire control panel enters Fault condition : Battery low;
Reset Panel
– initial reset of the fire control panel after start up or after exit of
Adjustment Mode;
Manual Set Param
– enter SetUp Mode;
Remote Set Param
– enter Remote mode for setting the fire control panel parameters
or line parameters via the interface;
Battery Off
– back up batteries switched off due to interruption in mains supply;
Watchdog Reset
– the protection timer of the fire control panel is triggered.
Press and hold the button
to display information screen
for event’s date and time:
(The field
“HH:MM:SS” contains hour, minutes and seconds;
“DD-MM-YY ” contains day, month and year)
The screen is visualized when button
is being pressed and hold.
14. SetUp Mode
14.1. Description
SetUp Mode is used for setting configuration parameters of a fire control panel. Access is
provided through the screen of Information and Control Mode, menu System functions, submenu
SetUp (see section 13 - Information and Control Mode). When the fire control panel enters SetUp
Mode, it exits all other modes or conditions and the registered configuration is saved in the energy
independent memory. Upon exit of SetUp Mode the unit is reset.
When the fire control panel operates in SetUp Mode it does not serve fire alarm lines, controllable
outputs and the other periphery devices (all lines and outputs are switched off); the fire control panel
is controlled via the keypad for mode operation.
Archive NNN of XXX
HH:MM:SS DD-MM-YY