UniPOS
Fire Control Panel FS5200
Instruction manual
Page 51
Revision 8/07.17
of 69
e) Restore the power supply of the fire control panel by placing the fuse back in the terminal
with fuse (Appendix 3), connect the feeding cables to the backup batteries and close the
fire control panel;
f) The fire control panel proceeds to System operation and enters Fault condition: New
configuration;
g) Enter SetUp Mode and if necessary, re-configure the fire control panel. When SetUp
Mode is exited, the control panel runs again system operations and enters Duty Mode;
h) The unit is ready to provide site protection.
To remove Module 5201 from Additional Module follow the instructions:
a) Open the fire control panel and cut off the power supply by taking the fuse out of the
terminal with fuse (Appendix 3) and disconnecting the feeding cables of the backup
batteries;
b) Disconnect the fire alarm lines from Module 5201;
c) Unscrew the
М3 screws that fix Module 5201 and remove the module (Appendix 4b);
d) Restore the power supply of the fire control panel by placing the fuse back in the terminal
with fuse (Appendix 3), connect the feeding cables to the backup batteries and close the
fire control panel;
e) The fire control panel proceeds to System operation and enters Fault condition: New
configuration;
f) Enter SetUp Mode and if necessary, re-configure the fire control panel. When SetUp
Mode is exited, the control panel runs again system operations and enters Duty Mode;
g) The unit is ready to provide site protection.
21. Troubleshooting
Possible problems and methods of troubleshooting are described in Table 4.
Table 4
Trouble
Indication
Troubleshooting
Fatal System fault
(except for New
configuration)
Indicators
and
illuminate in
steady yellow light; the local sounder
releases continuous signal; the message
System Fault
is displayed;
The trouble shall be fixed in
Service department
New configuration
Indicator
flashes in yellow light,
indicator
illuminates in continuous
yellow light; local sounder produces
discontinuous signal, the message
New
configuration
appears on the screen
Enter SetUp Mode. Exit the
mode and if the problem
persists, it shall be fixed in
Service department
Low backup batteries
due to interrupted
mains power supply
The local sounder releases
discontinuous signal (1s sound, 3s
pause); the message
Battery Low
appears on the screen; the backlight of
the display is off
Restore the mains power supply
or replace the backup batteries
Fault in a line
Indicator
flashes in yellow light;
the local sounder releases discontinuous
signal; the message
Fault in Line
appears on the screen
- Eliminate the fault (short
circuit, interruption or removed
fire detector);
- In Fault condition: Removed
FD check for short circuit in a
component to a ground wire
(see
Fault condition: Short
circuit to ground wire
)