UniPOS
Fire Control Panel FS5200
Instruction manual
Page 23
Revision 8/07.17
of 69
Fault in the supply to external devices in Basic module:
(The
field “ЕEЕ” contains the number of the faults)
Fault in the supply to external devices in Additional
module:
(The field “ЕEЕ” contains the number of the faults)
When the fire control panel is in Fire condition, the messages for fault are suppressed.
To display the suppressed messages enter Information and Control Mode (see section 13.2).
10.3. Using the keypad
In fatal fault condition (except for New configuration) none of the buttons is active.
For the rest fault conditions 2 active buttons are supported. When the control panel operates in
combination with other conditions, their buttons are active too.
10.3.1. Button
(Alarm)
Press the button to:
Switch off the local sounder if it responded for Fire condition/Pre-Fire condition or Fault
condition;
Activate the local sounder if the Fire control panel is in Fire condition/Pre-Fire condition or
Fault condition and the local sounder is previously suppressed by the same button.
The LED indicator on the button is illuminated if the local sounder is switched off after it
responded for Fire condition/Pre-Fire condition or Fault condition.
The button does not affect nor is its action cancelled by the following events:
When Fire Condition is registered in a new line, or transition from Fire condition stage I to Fire
condition stage II the button shall activate the local sounder for Fire/Pre-Fire condition
When Pre-Fire Condition is registered in a new line, the button will activate the local sounder
for Fire/Pre-Fire condition;
When a new Fault condition is registered, the button shall activate the local sounder for Fault
condition only.
The button’s LED indicator remains illuminated if the signalization and/or outputs remain off.
The button is active at Access levels 1 and 2.
10.3.2. Button
(Menu)
Press the button to enter Information and Control Mode.
11. Disabled Component Mode
11.1. Description
The fire control panel enters Disabled Component Mode after a component has been manually
disabled
– a fire alarm line or a controllable output. The condition is controlled via the screens of
Information and Control Mode (see sections 13.7.6 and 13.7.7). The disabled line is switched off (the
power supply is cut off) and is not monitored for activated fire detector and faults. The disabled
controllable output is switched off (the executive device can not operate) and is not monitored for
faults.
In case of disabled fire alarm lines a relevant message is shown on the display.
Additional information is acquired from the LED indicators.
Duty 17:05:34
Flt:ЕEЕ Flt Out Pwr2
Duty 17:05:34
Flt:ЕEЕ Flt Out Pwr1