20. Change in fire control panel configuration
20.1. How to add or remove Additional Module
Fire control panel FS5200 is able to operate with one additional module having 8 or 16 fire alarm
line.
To add an additional module, follow the instructions:
a) Open the fire control panel and cut off the power supply by taking the fuse out of the
terminal with fuse (Appendix 3) and disconnecting the feeding cables of the backup
batteries ;
b) Connect the available ribbon cable to the connector of module 5202, Basic Module, and to
the connector of circuit board5200 Base, Basic Module (Appendix 6);
c) Fix the Additional Module in a way that the stud
on the panel’s bottom enters the provided
hole on the module
and the restricting strap on the panel’s bottom is in opposite direction
of the module’s slot (Appendix 6);
d) Slide the Additional Module down until rest (Appendix 6);
e) Drive the available Special nut onto the stud
on the panel’s bottom, provided for additional
modules and screw until rest (Appendix 6);
f) Connect the provided ground wire to the ground terminals of the module and to the bottom
of the panel (Appendix 6);
g) Connect the fire alarm lines or the executive devices to the newly added module
(Appendix 4);
h) Restore the power supply of the fire control panel by placing the fuse back in the terminal
with fuse (Appendix 3), connect the feeding cables to the backup batteries and close the
fire control panel;
i) The fire control panel proceeds to System operation and enters Fault condition: New
configuration;
j) Enter SetUp Mode and if necessary, re-configure the fire control panel. When SetUp
Mode is exited, the control panel runs again system operations and enters Duty Mode;
k) The unit is ready to provide site protection.
To remove an additional module, follow the instructions:
a) Open the fire control panel and cut off the power supply by taking the fuse out of the
terminal with fuse (Appendix 3) and disconnecting the feeding cables of the backup
batteries;
b) Disconnect the fire alarm lines or executive devices from the module you want to remove;
c) Disconnect the ground wire and the ground terminals of the module and of the panel
bottom (Appendix 6);
d) Unscrew the Special nut (Appendix 6);
e) Slide the Additional Module upwards so that the
restricting strap on the panel’s bottom
enters the
module’s slot (Appendix 6);
f) Take the Additional Module out;
g)
Disconnect the module’s ribbon cable from the connector of the Basic Module (Appendix
6);
h) Restore the power supply of the fire control panel by placing the fuse back in the terminal
with fuse (Appendix 3), connect the feeding cables to the backup batteries and close the
fire control panel;
i) The fire control panel proceeds to System operation and enters Fault condition: New
configuration;
j) Enter SetUp Mode and if necessary, re-configure the fire control panel. When SetUp
Mode is exited, the control panel runs again system operations and enters Duty Mode;
k) The unit is ready to provide site protection.
20.2. Change in Basic Module
The following changes can be made in Basic Module:
Add Module 5201 (8 fire alarm lines);
Add Module 5203 (8 relay outputs for fire condition) or Module 5204 (16 relay outputs for fire
condition);
Remove Module 5201 (8 fire alarm lines);